FIR08-00766
| INSP-Sprinkler Rough-in/Hydro | 3/3/2009 | 3/4/2009 | 3/4/2009 4:07:55 PM | P | PASS |
|
|
See the onsite plans for the locations inspected today.
|
FIR08-00675
| INSP-Sprinkler Rough-in/Hydro | 3/3/2009 | 3/4/2009 | 3/4/2009 4:06:43 PM | P | CANC |
|
|
UG Hydro Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
|
BLD08-01321
| FIRE-Final Inspection | 3/3/2009 | 3/4/2009 | 3/4/2009 4:03:54 PM | A | FAIL |
|
|
The only items inspected today was the exit signs/emergency lighting. See the city approved plans for locations where devices are missing or inoperative.
|
FIR08-00787
| INSP-Sprinkler Rough-in | 3/4/2009 | 3/4/2009 | 3/4/2009 4:01:51 PM | P | PASS |
|
|
Per Tim Frost the deficiencies have been corrected and the sprinkler piping can be covered.
|
BLD08-02248
| FIRE-Final Inspection | 3/3/2009 | 3/4/2009 | 3/4/2009 3:51:31 PM | A | FAIL |
|
|
Provide a fire alarm permit for the alarm system modifications required due to the deletion of the exit corridor. Provide a fire sprinkler permit for the deletion of the two pendant heads in the demo'd office. Fix the battery trouble on the existing fire alarm panel. Provide the missing door hardware. Repair the existing emergency light at the bottom of the stairs.
|
FIR08-00672
| INSP-Final Inspection | 3/3/2009 | 3/4/2009 | 3/4/2009 3:45:06 PM | A | FAIL |
|
|
Still need the annual inspection for the existing fire sprinkler risers performed.
|
BLD09-00185
| FIRE-Final Inspection | 3/3/2009 | 3/4/2009 | 3/4/2009 3:43:44 PM | A | FAIL |
|
|
The exit signs have not been provided with battery backup. All other items have been addressed.
|
FIR08-00788
| INSP-Final Inspection | 3/3/2009 | 3/4/2009 | 3/4/2009 3:42:34 PM | A | FAIL |
|
|
Contractor was not ready for inspection.
|
FIR08-00735
| INSP-Supply line flush | 3/3/2009 | 3/4/2009 | 3/4/2009 11:09:30 AM | A | PASS |
|
|
Underground flush passed.
|
FIR09-00145
| INSP-Sprinkler Rough-in | 3/3/2009 | 3/4/2009 | 3/4/2009 8:15:10 AM | A | PASS |
|
|
Rough-in passed the sprinkler piping can be covered.
|
FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 3/2/2009 | 3/4/2009 | 3/4/2009 7:31:40 AM | A | CANC |
|
|
24 Air Test Floors 3-4 canceled due to a leak
|
FIR08-00735
| INSP-Sprinkler Rough-in/Hydro | 3/3/2009 | 3/4/2009 | 3/3/2009 11:52:46 AM | A | CANC |
|
|
Ryan is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|