BLD10-00305
| FIRE-Final Inspection | 3/4/2010 | 3/4/2010 | 3/4/2010 6:02:23 PM | P | DONE |
|
|
For verification of building address numbers posted and panic hardware at the dining area second exits.
|
BLD10-00066
| FIRE-Final Inspection | 3/4/2010 | 3/4/2010 | 3/4/2010 5:59:59 PM | P | PASS |
|
|
Scope of permit work passed inspection. Life safety finaled.
|
BLD10-00065
| FIRE-Final Inspection | 3/3/2010 | 3/4/2010 | 3/4/2010 5:59:05 PM | A | PASS |
|
|
Life safety inspection completed satisfactory, fire extinguishers serviced while on site, contractor provided missing signage at the main entry/exit door as requested.
|
BLD10-00022
| FIRE-Final Inspection | 3/4/2010 | 3/4/2010 | 3/4/2010 5:56:43 PM | P | PASS |
|
|
Reinspection passed, correction items verified for completion. Fire life safety is acceptable.
|
BLD09-02227
| FIRE-Conference | 3/4/2010 | 3/4/2010 | 3/4/2010 5:55:07 PM | P | DONE |
|
|
Regarding project related FIR10-00091 pipe materials.
|
BLD10-00022
| FIRE-Final Inspection | 3/4/2010 | 3/4/2010 | 3/4/2010 5:53:11 PM | A | FAIL |
|
|
C/N items included exit signs at two locations to be repaired, provide EM lighting at the back exitway adjacent to the restrooms per plan annotations, repair one EM light, remove address numbers 611 at the second exit door facing main street.
|
FIR10-00045
| INSP-Final Inspection | 3/3/2010 | 3/4/2010 | 3/4/2010 5:48:19 PM | A | PASS |
|
|
Hood suppression system operated correctly under test conditions, permit final okay.
|