FIR03-00082
| FIR-Aging Inspection | 3/4/2010 | 3/4/2010 | 3/8/2010 3:15:22 PM | | NR |
|
|
Information forwarded to Scott for further action with nonreponsive contractor.
|
FIR03-00052
| FIR-Aging Inspection | 3/4/2010 | 3/4/2010 | 3/8/2010 3:15:04 PM | | NR |
|
|
Information forwarded to Scott for further action with nonreponsive contractor.
|
BLD10-00152
| FIRE-Final Inspection | 3/4/2010 | 3/4/2010 | 3/4/2010 3:31:20 PM | A | CANC |
|
|
When the signage is provided on the fire alarm access door and signage is provided on the fire sprinkler riser door, the project related fire alarm permit is passed the life can be passed for this project.
|
FIR09-00674
| INSP-Final Inspection | 3/4/2010 | 3/4/2010 | 3/4/2010 3:26:08 PM | P | FAIL |
|
|
Provide a map at the facp as discussed, provide corrected address at the monitoring station, provide as-builts that show the manual pull and smoke detector combined on zone 1, with zone 2 as a tamper, zone three as a PIV and zone 4 as the flow switch. Change out the submittal data sheet for the AES panel from a model 7750 to the 7788 which was actually installed. NetCon was a 5. All other items are passed.
|
FIR09-00600
| INSP-Final Inspection | 3/3/2010 | 3/4/2010 | 3/4/2010 3:16:52 PM | P | PASS |
|
|
Permit finaled
|
BLD10-00384
| FIRE-Final Inspection | 3/3/2010 | 3/4/2010 | 3/4/2010 2:13:50 PM | A | PASS |
|
|
Life safety passed
|
BLD10-00395
| FIRE-Final Inspection | 3/3/2010 | 3/4/2010 | 3/4/2010 10:25:11 AM | A | FAIL |
|
|
See the red line comments written on the city approved floor plan. Items include the repair of existing exit signs and providing additional emergency lighting in the conference and break rooms.
|
FIR10-00048
| INSP-Final Inspection | 3/3/2010 | 3/4/2010 | 3/4/2010 10:20:54 AM | A | PASS |
|
|
Permit finaled
|