BLD10-02374
| FIRE-Final Inspection | 3/4/2011 | 3/4/2011 | 3/4/2011 3:27:09 PM | P | PASS |
|
|
Life safety passed.
|
FIR11-00037
| INSP-Final Inspection | 3/4/2011 | 3/4/2011 | 3/4/2011 2:30:44 PM | P | PASS |
|
|
Permit finaled
|
BLD10-02374
| FIRE-Final Inspection | 3/3/2011 | 3/4/2011 | 3/4/2011 10:25:20 AM | A | FAIL |
|
|
Provide final for the project related fire alarm permit. Remove the dead bolt on the office door and remove the outdated fire extinguisher in the break room.
|
FIR11-00037
| INSP-Final Inspection | 3/3/2011 | 3/4/2011 | 3/4/2011 9:36:24 AM | A | FAIL |
|
|
Seven smoke detectors have been located too close to air registers. One strobes candella has not been set correctly. Phone lines, wire guage, a/v sync and EOL has been verified correct.
|
FIR11-00037
| FIR-Aging Inspection | 3/4/2011 | 3/4/2011 | 3/4/2011 9:33:24 AM | P | CANC |
|
|
Wrong inspection type set up.
|