BLD14-01578
| FIRE-Final Inspection | 3/4/2015 | 3/4/2015 | 3/4/2015 5:13:16 PM | P | PART |
|
|
Final pending completion of elevator and related control equipment. Remainder of fire life safety inspection items completed. Need to post missing building address numbers.
|
FIR14-00908
| INSP-Final Inspection | 3/4/2015 | 3/4/2015 | 3/4/2015 5:11:17 PM | P | PASS |
|
|
Inspection passed. Fire alarm permit finaled.
|
FIR14-00317
| INSP-Final Inspection | 3/4/2015 | 3/4/2015 | 3/4/2015 5:09:44 PM | A | PASS |
|
|
Fire alarm work passed field testing and inspection. Permit finaled.
|
FIR14-00723
| INSP-Final Inspection | 3/3/2015 | 3/4/2015 | 3/4/2015 5:08:12 PM | A | PART |
|
|
Final pending remainder of elevator installation and associated control equipment. Duct detectors, smoke at panel, batteries, and power supply tested okay. Need to provide signage at the door to the FACP room, record of completion documents at final.
|
BLD15-00470
| FIRE-Final Inspection | 3/3/2015 | 3/4/2015 | 3/4/2015 10:52:54 AM | A | FAIL |
|
|
Modifications to the existing fire alarm and fire sprinkler systems will be necessary prior to occupancy approval. Permits will be required for this work as discussed. Need to post a fire extinguisher within allowable travel distance.
|