ELE15-03800
| Final | 3/4/2016 | 3/4/2016 | 3/4/2016 2:23:42 PM | P | PASS |
|
|
Turn on breaker, photo cell is taped on. Phone #: ###-#### Inspection requested via web by Eric Brown pedastal final ok
|
ELE15-04033
| Final | 3/4/2016 | 3/4/2016 | 3/4/2016 2:22:06 PM | P | PASS |
|
|
Turn on breaker, photo cell is taped on. Phone #: ###-#### Inspection requested via web by Eric Brown pedastal final ok
|
ELE16-00547
| Permanent Service | 3/3/2016 | 3/4/2016 | 3/4/2016 2:04:28 PM | P | FAIL |
|
|
Rocky Phone #: ###-#### 300.4 bored holes within 1 1/4" within of framing member shall have a listed nailplate 334.30 type NM cable shall be supported ever 4 1/2"
|
ELE15-03839
| Final | 3/4/2016 | 3/4/2016 | 3/4/2016 1:35:14 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov final ok
|
ELE16-00688
| Final | 3/4/2016 | 3/4/2016 | 3/4/2016 12:40:47 PM | P | PASS |
|
|
circuit for electric car Phone #: ###-#### Inspection requested via web by Randy Fletcher final for car chargeing receptacles ok
|
ELE15-00685
| Final | 3/2/2016 | 3/4/2016 | 3/4/2016 11:58:26 AM | A | CANC |
|
|
Final inspection please. Please contact Gary Allen prior to arrival at ###-#### as he will have a key to let you in. If you have any electrical questions please contact David Forbes at ###-#### as he will not be at this location. Thank you so much and have a super day! Phone #: ###-#### Inspection requested via web by Laura Longshaw called and no one answered nor a phone call back
|
ELE16-00586
| Electrical Rough-In | 3/4/2016 | 3/4/2016 | 3/4/2016 11:44:02 AM | P | PASS |
|
|
Panel and Inverter Listing Inspection Phone #: ###-#### Inspection requested via web by Ryan King verified listing of panels and inverters all listed
|
ELE16-00692
| Rough-In Permanent Service | 3/4/2016 | 3/4/2016 | 3/4/2016 11:31:06 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI rough-in ok cover p/s u/g n ok
|
ELE15-03423
| Rough-In Permanent Service | 3/4/2016 | 3/4/2016 | 3/4/2016 11:04:58 AM | P | CANC |
|
|
Rough in inspection for service cabinet on interior of complex at north east corner for building located farthest to the southeast. 2x3 Cabinet base is formed ready for concrete. Phone #: ###-#### Inspection requested via web by steve ragan just needed rough-in for concrete pour
|
ELE15-03423
| Electrical Rough-In | 3/4/2016 | 3/4/2016 | 3/4/2016 11:04:39 AM | P | PASS |
|
|
Rough in inspection for service cabinet on interior of complex at north east corner for building located farthest to the southeast. 2x3 Cabinet base is formed ready for concrete. Phone #: ###-#### Inspection requested via web by steve ragan meter cabinet base ok to pour
|
ELE15-02742
| Final | 3/4/2016 | 3/4/2016 | 3/4/2016 10:46:32 AM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman 408.4 circuit directory shall be indentified 210.8(a)(2) garage receptacles shall have GFCI protection 210.8(a)(3) outdoor receptacles shall have GFCI protection 210.8(a)(6) kitchen receptacles shall have GFCI protection(cant verify it nor locate the GFCI 406.5 receptacle mounting shall be secured(few are loose in laundry) entry recept and out light in-op
|
ELE16-00601
| Temporary Service | 3/4/2016 | 3/4/2016 | 3/4/2016 10:03:35 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman t/s u/g n ok
|
ELE16-00676
| Permanent Service | 3/3/2016 | 3/4/2016 | 3/4/2016 9:54:32 AM | A | PASS |
|
|
Service inspection for Boise City pole light power pedestal Contact Tracy ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson p/s u/g n ok
|
ELE16-00669
| Rough-In Permanent Service | 3/2/2016 | 3/4/2016 | 3/4/2016 9:36:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by George Pascua whole house remodel ok cover
|
ELE16-00669
| Electrical Rough-In | 3/4/2016 | 3/4/2016 | 3/4/2016 9:35:44 AM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by George Pascua temporary receptacles shall have GFCI protection
|
ELE15-00923
| Final | 3/2/2016 | 3/4/2016 | 3/4/2016 9:05:59 AM | A | FAIL |
|
|
Owner would like to meet at 8:30 am. Phone #: ###-#### Inspection requested via web by Alan Lusk 334.15 type NM cable in exposed work shall be protected from physical damage 342.30 IMC shall be fastened within 3' of a cabinet 406.6 faceplates required basement room receptacles in-op
|
ELE16-00676
| Final | 3/3/2016 | 3/4/2016 | 3/3/2016 3:37:08 PM | A | CANC |
|
|
Inspection for light pole power pedestal (Boise City pole lights) Contact: Tracy ###-#### Phone #: ###-#### >> Inspection requested via web by Tracy Robertson Inspection cancelled from web by: Tracy Robertson
|