Inspections for the day of: Friday, March 4, 2016.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03800 Final3/4/20163/4/20163/4/2016 2:23:42 PMPPASS
Turn on breaker, photo cell is taped on. Phone #: ###-#### Inspection requested via web by Eric Brown pedastal final ok
ELE15-04033 Final3/4/20163/4/20163/4/2016 2:22:06 PMPPASS
Turn on breaker, photo cell is taped on. Phone #: ###-#### Inspection requested via web by Eric Brown pedastal final ok
ELE16-00547 Permanent Service3/3/20163/4/20163/4/2016 2:04:28 PMPFAIL
Rocky Phone #: ###-#### 300.4 bored holes within 1 1/4" within of framing member shall have a listed nailplate 334.30 type NM cable shall be supported ever 4 1/2"
ELE15-03839 Final3/4/20163/4/20163/4/2016 1:35:14 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov final ok
ELE16-00688 Final3/4/20163/4/20163/4/2016 12:40:47 PMPPASS
circuit for electric car Phone #: ###-#### Inspection requested via web by Randy Fletcher final for car chargeing receptacles ok
ELE15-00685 Final3/2/20163/4/20163/4/2016 11:58:26 AMACANC
Final inspection please. Please contact Gary Allen prior to arrival at ###-#### as he will have a key to let you in. If you have any electrical questions please contact David Forbes at ###-#### as he will not be at this location. Thank you so much and have a super day! Phone #: ###-#### Inspection requested via web by Laura Longshaw called and no one answered nor a phone call back
ELE16-00586 Electrical Rough-In3/4/20163/4/20163/4/2016 11:44:02 AMPPASS
Panel and Inverter Listing Inspection Phone #: ###-#### Inspection requested via web by Ryan King verified listing of panels and inverters all listed
ELE16-00692 Rough-In Permanent Service3/4/20163/4/20163/4/2016 11:31:06 AMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI rough-in ok cover p/s u/g n ok
ELE15-03423 Rough-In Permanent Service3/4/20163/4/20163/4/2016 11:04:58 AMPCANC
Rough in inspection for service cabinet on interior of complex at north east corner for building located farthest to the southeast. 2x3 Cabinet base is formed ready for concrete. Phone #: ###-#### Inspection requested via web by steve ragan just needed rough-in for concrete pour
ELE15-03423 Electrical Rough-In3/4/20163/4/20163/4/2016 11:04:39 AMPPASS
Rough in inspection for service cabinet on interior of complex at north east corner for building located farthest to the southeast. 2x3 Cabinet base is formed ready for concrete. Phone #: ###-#### Inspection requested via web by steve ragan meter cabinet base ok to pour
ELE15-02742 Final3/4/20163/4/20163/4/2016 10:46:32 AMPFAIL
Phone #: ###-#### Inspection requested via web by Brandon Hillman 408.4 circuit directory shall be indentified 210.8(a)(2) garage receptacles shall have GFCI protection 210.8(a)(3) outdoor receptacles shall have GFCI protection 210.8(a)(6) kitchen receptacles shall have GFCI protection(cant verify it nor locate the GFCI 406.5 receptacle mounting shall be secured(few are loose in laundry) entry recept and out light in-op
ELE16-00601 Temporary Service3/4/20163/4/20163/4/2016 10:03:35 AMPPASS
Phone #: ###-#### Inspection requested via web by Brandon Hillman t/s u/g n ok
ELE16-00676 Permanent Service3/3/20163/4/20163/4/2016 9:54:32 AMAPASS
Service inspection for Boise City pole light power pedestal
Contact Tracy ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson p/s u/g n ok
ELE16-00669 Rough-In Permanent Service3/2/20163/4/20163/4/2016 9:36:03 AMAPASS
Phone #: ###-#### Inspection requested via web by George Pascua whole house remodel ok cover
ELE16-00669 Electrical Rough-In3/4/20163/4/20163/4/2016 9:35:44 AMPFAIL
Phone #: ###-#### Inspection requested via web by George Pascua temporary receptacles shall have GFCI protection
ELE15-00923 Final3/2/20163/4/20163/4/2016 9:05:59 AMAFAIL
Owner would like to meet at 8:30 am. Phone #: ###-#### Inspection requested via web by Alan Lusk 334.15 type NM cable in exposed work shall be protected from physical damage 342.30 IMC shall be fastened within 3' of a cabinet 406.6 faceplates required basement room receptacles in-op
ELE16-00676 Final3/3/20163/4/20163/3/2016 3:37:08 PMACANC
Inspection for light pole power pedestal (Boise City pole lights)
Contact: Tracy ###-#### Phone #: ###-#### >> Inspection requested via web by Tracy Robertson Inspection cancelled from web by: Tracy Robertson