Inspections for the day of: Wednesday, March 5, 2003.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-00557 Electrical Rough-In3/4/20033/5/20033/5/2003 12:00:00 AMAPART
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung u/g ok 3/5/2003 8:34:19 AM
ELE01-02928 Final3/4/20033/5/20033/5/2003 12:00:00 AMAPASS
SCOTT; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 3/5/2003 2:40:30 PM
ELE02-01458 Electrical Rough-In3/4/20033/5/20033/5/2003 12:00:00 AMAPART
TOM; Phone #: ###-#### Internet Inspection Request from: Annette Moore rest rm r/i ok and final and ceiling cover for rms 108,109,110,110A 3/5/2003 9:32:01 AM
ELE03-00116 Electrical Rough-In3/5/20033/5/20033/5/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 3/5/2003 at 8:10:41 AM. Contact: ###-####. walls and soffits reception area 3/5/2003 4:09:25 PM
ELE02-03770 Final3/5/20033/5/20033/5/2003 12:00:00 AMPPASS
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 3/5/2003 1:05:01 PM
ELE01-03900 Final3/5/20033/5/20033/5/2003 12:00:00 AMPFAIL
###-#### eric cor. posted art.100 bathrooms, 240-24(e) no overcurrent devices shall be installed in dwelling bathrooms, 210-8(a)(1) gfci for all recept outlets in bathrooms needs shower trim M bath, and gfci for elevator pit recept, correction for low voltage phone in elevator cabinet shall have same volt rating as high volt 300-3(c) met with contractor 3/5/2003 2:47:19 PM
ELE03-00457 Electrical Rough-In3/4/20033/5/20033/5/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 3/4/2003 at 8:38:39 AM. Contact: ###-####. part u/g for core and shell only 3/5/2003 3:28:53 PM
ELE03-00613 Final3/4/20033/5/20033/5/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 3/4/2003 at 8:58:30 AM. Contact: ###-####. ok 3/5/2003 1:25:18 PM