ELE03-00557
| Electrical Rough-In | 3/4/2003 | 3/5/2003 | 3/5/2003 12:00:00 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung u/g ok 3/5/2003 8:34:19 AM
|
ELE01-02928
| Final | 3/4/2003 | 3/5/2003 | 3/5/2003 12:00:00 AM | A | PASS |
|
|
SCOTT; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 3/5/2003 2:40:30 PM
|
ELE02-01458
| Electrical Rough-In | 3/4/2003 | 3/5/2003 | 3/5/2003 12:00:00 AM | A | PART |
|
|
TOM; Phone #: ###-#### Internet Inspection Request from: Annette Moore rest rm r/i ok and final and ceiling cover for rms 108,109,110,110A 3/5/2003 9:32:01 AM
|
ELE03-00116
| Electrical Rough-In | 3/5/2003 | 3/5/2003 | 3/5/2003 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 3/5/2003 at 8:10:41 AM. Contact: ###-####. walls and soffits reception area 3/5/2003 4:09:25 PM
|
ELE02-03770
| Final | 3/5/2003 | 3/5/2003 | 3/5/2003 12:00:00 AM | P | PASS |
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 3/5/2003 1:05:01 PM
|
ELE01-03900
| Final | 3/5/2003 | 3/5/2003 | 3/5/2003 12:00:00 AM | P | FAIL |
|
|
###-#### eric cor. posted art.100 bathrooms, 240-24(e) no overcurrent devices shall be installed in dwelling bathrooms, 210-8(a)(1) gfci for all recept outlets in bathrooms needs shower trim M bath, and gfci for elevator pit recept, correction for low voltage phone in elevator cabinet shall have same volt rating as high volt 300-3(c) met with contractor 3/5/2003 2:47:19 PM
|
ELE03-00457
| Electrical Rough-In | 3/4/2003 | 3/5/2003 | 3/5/2003 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 3/4/2003 at 8:38:39 AM. Contact: ###-####. part u/g for core and shell only 3/5/2003 3:28:53 PM
|
ELE03-00613
| Final | 3/4/2003 | 3/5/2003 | 3/5/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/4/2003 at 8:58:30 AM. Contact: ###-####. ok 3/5/2003 1:25:18 PM
|