ELE06-01002
| DOC - Permit Expired | 3/5/2007 | 3/5/2007 | 3/5/2007 1:24:25 PM | P | PASS |
|
|
called a number of times no response
|
ELE06-02008
| Final | 3/5/2007 | 3/5/2007 | 3/5/2007 1:21:42 PM | P | PASS |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Victoria Beall shell core r/i for ceiling ok final ok card signed
|
ELE07-00696
| Temporary Service | 3/2/2007 | 3/5/2007 | 3/5/2007 12:36:56 PM | P | PASS |
|
|
neil; Phone #: ###-#### Internet Inspection Request from: Victoria Beall t/s o/h new ok
|
ELE07-00609
| Rough-In Permanent Service | 3/2/2007 | 3/5/2007 | 3/5/2007 10:08:31 AM | A | PASS |
|
|
brad- ###-#### r/i p/s u/g new ok for shell and house panel meter only
|
ELE07-00637
| Permanent Service | 3/1/2007 | 3/5/2007 | 3/5/2007 9:18:52 AM | A | FAIL |
|
|
Service Change, panel and new meter only Phone #: ###-#### corrr. called 250.52(A)(1)&104(A)(1) grd and bond water system U/G pipe and hot&cold, 230.6 shall not have service entrance conductors inside house (4 foot of flex inside from meter, watch range and dryer from sub panel
|
ELE07-00602
| Rough-In Permanent Service | 3/5/2007 | 3/5/2007 | 3/5/2007 8:33:25 AM | A | PASS |
|
|
r/i p/s u/g new ok
|
ELE06-03281
| Electrical Rough-In | 3/2/2007 | 3/5/2007 | 3/5/2007 8:32:15 AM | A | FAIL |
|
|
Please inspect 1st floor rough-in at A-wing. Thankyou. Phone #: ###-#### met contr not ready outlet spacing, and remove duct tape from flex at panel 300.10 elect. continunity
|