PLM07-00390
| Final | 3/2/2007 | 3/5/2007 | 3/5/2007 4:23:13 PM | P | PART |
|
|
JOB CONTACT RANDY REEVES: PHONE NUMBER ###-#### Phone #: ###-####-trim passes, need to have c/o's in slab flush with concrete.
|
PLM07-00569
| Sprinkler (Final) | 3/2/2007 | 3/5/2007 | 3/5/2007 3:53:55 PM | P | PASS |
|
|
jose late afternoon; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
PLM07-00587
| Water and/or Sewer | 3/5/2007 | 3/5/2007 | 3/5/2007 3:46:01 PM | P | PASS |
|
|
chad ###-####
|
PLM07-00587
| DOC - Permit Finaled | 3/5/2007 | 3/5/2007 | 3/5/2007 3:45:45 PM | P | PASS |
|
|
|
PLM07-00554
| Plumbing Rough-in | 3/5/2007 | 3/5/2007 | 3/5/2007 3:30:46 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/5/2007 at 7:33:18 AM. Contact: ###-####.-dwv test failed, cannot glue c/o plugs, add c/o on washer drain, island sink vent needs to be graded, need 1/4" grade on horizontal drainage, vents shall be level or graded,
|
PLM07-00527
| Plumbing Rough-in | 3/2/2007 | 3/5/2007 | 3/5/2007 2:42:28 PM | P | PART |
|
|
Phone #: ###-####-right side passes, left side dwv & water test failed, san tee above tub for vent is in backwards.
|
PLM07-00564
| Plumbing Rough-in | 3/5/2007 | 3/5/2007 | 3/5/2007 1:32:25 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/5/2007 at 9:06:44 AM. Contact: ###-####.
|
PLM07-00187
| Water and/or Sewer | 3/5/2007 | 3/5/2007 | 3/5/2007 11:18:28 AM | P | PASS |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM07-00187
| DOC - Permit Finaled | 3/5/2007 | 3/5/2007 | 3/5/2007 11:18:04 AM | P | PASS |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM07-00188
| Water and/or Sewer | 3/5/2007 | 3/5/2007 | 3/5/2007 11:17:17 AM | P | PASS |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM07-00188
| DOC - Permit Finaled | 3/5/2007 | 3/5/2007 | 3/5/2007 11:16:57 AM | P | PASS |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM07-00189
| Water and/or Sewer | 3/5/2007 | 3/5/2007 | 3/5/2007 11:16:17 AM | P | PASS |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM07-00189
| DOC - Permit Finaled | 3/5/2007 | 3/5/2007 | 3/5/2007 11:15:57 AM | P | PASS |
|
|
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM06-01299
| PLM-Aging Inspection | 3/5/2007 | 3/5/2007 | 3/5/2007 10:57:46 AM | | PASS |
|
|
|
PLM06-01654
| PLM-Aging Inspection | 3/5/2007 | 3/5/2007 | 3/5/2007 10:57:35 AM | | PASS |
|
|
|
PLM06-01008
| PLM-Aging Inspection | 3/5/2007 | 3/5/2007 | 3/5/2007 10:57:23 AM | | PASS |
|
|
|
PLM06-01968
| Final | 3/2/2007 | 3/5/2007 | 3/5/2007 9:45:27 AM | A | PART |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Patricia Smith-proofers need to be on there own rpbp, ovens need to be on there own rpbp, need exspantion tank, rpbp's need tested & certified.
|
PLM07-00514
| Plumbing Rough-in | 3/2/2007 | 3/5/2007 | 3/5/2007 8:58:44 AM | A | PASS |
|
|
todd; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|