Inspections for the day of: Monday, March 5, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00178 INSP-Final Inspection3/5/20073/5/20073/5/2007 5:27:41 PMPPASS
permit finaled
FIR06-00777 INSP-Supply line flush3/2/20073/5/20073/5/2007 4:24:50 PMPPASS
The underground flush for the new building passed. The underground supply for the future building was not flushed.
FIR06-00777 INSP-Sprinkler Rough-in/Hydro3/2/20073/5/20073/5/2007 4:23:51 PMPPASS
The underground hydro for the new building passed but had to be measured for leakage. The underground supply for the future building was not tested.
BLD06-02534 FIRE-Final Inspection3/5/20073/5/20073/5/2007 2:53:13 PMPCANC
Fire alarm is not ready yet. No inspection was performed.
BLD06-00212 FIRE-Final Inspection3/5/20073/5/20073/5/2007 2:51:50 PMPCANC
Fire alarm is not ready yet. No inspection was performed.
FIR06-00466 INSP-Final Inspection3/5/20073/5/20073/5/2007 2:50:43 PMPFAIL
We finished testing the duct smoke detectors. One detector located in the 2nd floor break room is mounted in a 90. It will need to be relocated or provide a manometer test. The two tamper switches for both risers did not operate. The PIV tamper did.The west side wet system flow switch operated correctly but the east side inspectors test did not have the correct orfice installed and will need to be retested. To finish project the items listed above need corrected and the notification circuits need to be tested as far as voltage drop and trouble signals as well as device spacing and sound levels. Battery calcs have not been done/verified yet either.
MIS06-00243 FIR-Final3/5/20073/5/20073/5/2007 1:40:02 PMPPASS
Life safety finaled
FIR07-00178 INSP-Sprinkler Rough-in3/2/20073/5/20073/5/2007 12:25:46 PMAPASS
Rough-in passed
FIR07-00082 INSP-Final Inspection3/5/20073/5/20073/5/2007 11:43:00 AMPPASS
permit finaled
FIR07-00082 INSP-Final Inspection3/5/20073/5/20073/5/2007 11:14:45 AMPPART
permit finaled
FIR05-00536 INSP-Sprinkler Rough-in3/2/20073/5/20073/5/2007 10:13:25 AMAPASS
See the city approved plans for locations of piping above hardlids that is approved for cover