Inspections for the day of: Wednesday, March 5, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-01014 INSP-Final Inspection3/4/20083/5/20083/5/2008 5:56:49 PMPPASS
Fire alarm system modifications passed field testing, some minor adjustments made while on site, accepted as-built plans for two field changes, permit finaled.
BLD07-02335 FIRE-Final Inspection3/4/20083/5/20083/5/2008 5:54:58 PMANR
Need project related fire sprinkler permit finaled prior to building life safety approval, noted sprinkler permit is not yet issued. Reviewed with contractor noted defficient items to be amended prior to life safety final.
FIR07-00967 FIR-Aging Inspection3/5/20083/5/20083/5/2008 3:41:55 PM DEFR
On site visit, work appears complete, need field inspection request for permit final.
FIR07-00907 INSP-Conference3/5/20083/5/20083/5/2008 2:59:19 PMPDONE
Regarding site inspection scheduling.
FIR08-00071 INSP-Sprinkler Rough-in3/5/20083/5/20083/5/2008 2:54:48 PMPPART
See approved plans for areas initialed with today's date okayed for cover at the hard lid ceilings for the east remodel area.
FIR07-00891 INSP-Final Inspection3/3/20083/5/20083/5/2008 2:52:51 PMAPASS
Field testing passed, fire alarm permit finaled.
FIR07-00606 INSP-Sprinkler Rough-in/Hydro3/5/20083/5/20083/5/2008 12:15:01 PMAFAIL
Overhead rough-in inspection completed for the first floor areas E and F, noted some defficient items including missing EQ bracing, need to provide correct seismic clearance at two locations where 4" main meets block walls, remove the ball valve in the piping to the elevator pit sprinkler, the electrical rooms and storage areas under stairways are not yet complete, some hangers will need replaced due to damage, missing retaining straps installed while on site, noted possible overspacing at heads in the corridors due to adjacent vestibules, head at the trophy case wall recess may not be required.
FIR08-00072 INSP-Final Inspection3/4/20083/5/20083/5/2008 12:04:54 PMAPASS
Noted corrections verified for completion, final fire alarm testing passed, permit finaled.