FIR07-01014
| INSP-Final Inspection | 3/4/2008 | 3/5/2008 | 3/5/2008 5:56:49 PM | P | PASS |
|
|
Fire alarm system modifications passed field testing, some minor adjustments made while on site, accepted as-built plans for two field changes, permit finaled.
|
BLD07-02335
| FIRE-Final Inspection | 3/4/2008 | 3/5/2008 | 3/5/2008 5:54:58 PM | A | NR |
|
|
Need project related fire sprinkler permit finaled prior to building life safety approval, noted sprinkler permit is not yet issued. Reviewed with contractor noted defficient items to be amended prior to life safety final.
|
FIR07-00967
| FIR-Aging Inspection | 3/5/2008 | 3/5/2008 | 3/5/2008 3:41:55 PM | | DEFR |
|
|
On site visit, work appears complete, need field inspection request for permit final.
|
FIR07-00907
| INSP-Conference | 3/5/2008 | 3/5/2008 | 3/5/2008 2:59:19 PM | P | DONE |
|
|
Regarding site inspection scheduling.
|
FIR08-00071
| INSP-Sprinkler Rough-in | 3/5/2008 | 3/5/2008 | 3/5/2008 2:54:48 PM | P | PART |
|
|
See approved plans for areas initialed with today's date okayed for cover at the hard lid ceilings for the east remodel area.
|
FIR07-00891
| INSP-Final Inspection | 3/3/2008 | 3/5/2008 | 3/5/2008 2:52:51 PM | A | PASS |
|
|
Field testing passed, fire alarm permit finaled.
|
FIR07-00606
| INSP-Sprinkler Rough-in/Hydro | 3/5/2008 | 3/5/2008 | 3/5/2008 12:15:01 PM | A | FAIL |
|
|
Overhead rough-in inspection completed for the first floor areas E and F, noted some defficient items including missing EQ bracing, need to provide correct seismic clearance at two locations where 4" main meets block walls, remove the ball valve in the piping to the elevator pit sprinkler, the electrical rooms and storage areas under stairways are not yet complete, some hangers will need replaced due to damage, missing retaining straps installed while on site, noted possible overspacing at heads in the corridors due to adjacent vestibules, head at the trophy case wall recess may not be required.
|
FIR08-00072
| INSP-Final Inspection | 3/4/2008 | 3/5/2008 | 3/5/2008 12:04:54 PM | A | PASS |
|
|
Noted corrections verified for completion, final fire alarm testing passed, permit finaled.
|