Inspections for the day of: Thursday, March 5, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-02384 FIRE-Final Inspection3/4/20093/5/20093/5/2009 3:51:06 PMPPASS
life safety passed
FIR09-00018 INSP-Final Inspection3/5/20093/5/20093/5/2009 2:54:11 PMPPASS
Permit finaled
FIR08-00491 INSP-Final Inspection3/4/20093/5/20093/5/2009 2:52:58 PMAFAIL
This permit will be ok to final when the fire alarm interconnects have been verified.
BLD08-01321 FIRE-Final Inspection3/4/20093/5/20093/5/2009 2:51:37 PMAFAIL
The project related fire alarm permit needs to be finaled. Mount the occupant load signs, provide signage on the riser room and facp rooms as discussed. Provide exit discharge light at the main exit.
FIR08-00788 INSP-Final Inspection3/4/20093/5/20093/5/2009 2:50:10 PMAFAIL
The strobes in the BreakRoom and the Mens Locker Room did not work. The strobes in Corridor 138C did not sync. The strobes in the Women's locker room need to be sync'd or a hydraulic closer installed on the door as discussed. The fire/smoke dampers need inspected.
FIR08-00672 INSP-Final Inspection3/4/20093/5/20093/5/2009 2:27:58 PMAPASS
Permit finaled.
FIR08-00616 INSP-Sprinkler Rough-in/Hydro3/5/20093/5/20093/5/2009 2:27:12 PMAPASS
The remaining sprinkler piping is ok to cover.
FIR08-00688 INSP-Final Inspection3/4/20093/5/20093/5/2009 1:26:03 PMAFAIL
Provide as-builts showing the relocated smoke detectors, relocated NAC panel and the facp interconnection with the hvac shutdown.