Inspections for the day of: Monday, March 5, 2012.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS12-00041 FIR-Conference3/5/20123/5/20123/5/2012 3:22:06 PMPDONE
I stopped at this business and met with Ed Gracanin about work that has been performed without permits. The work appears to atleast include at small room built on a second floor/mezzanin with new stairs serving the room. I let him know that building and fire permits would be required and quite possibly electrical and mechanical permits. I also went over general life safety requirements such as door hardware and annual inspections for the fire systems and fire extinguishers. He was going to contact plan review in the morning to see what needs to be submitted.
BLD11-02987 FIRE-Final Inspection3/5/20123/5/20123/5/2012 3:01:52 PMPFAIL
Mount and tag the fire extinguishers, repair the smoke evac damper in space 1147, adjust the damper in space 1143, replace the exit sign at the rear exit door in space 1143 and provide sticker over the main exit door in space 1143.
FIR11-00691 INSP-Final Inspection3/2/20123/5/20123/5/2012 11:09:22 AMAFAIL
The south most basement branchline has upright sprinkler heads that are blocked by beams that have been wrapped in sheet rock. It appears that by turning the branchlines and installing pendants that most of the problem will be fixed. Also on this same branchline the southwest end head is located too far from the wall but relocating it closer to the wall will fix this problem as long as 130 sq. ft. is not exceeded. I will need as-built drawings showing these changes prior to a final sign off.