ELE12-01275
| ELE-Aging Inspection | 3/5/2014 | 3/5/2014 | 3/7/2014 3:00:18 PM | | DONE |
|
|
called, contractor will check for final
|
ELE14-00451
| Electrical Rough-In | 3/5/2014 | 3/5/2014 | 3/5/2014 3:08:31 PM | P | PART |
|
|
Phone #: ###-#### >> Inspection requested via web by Eric Brown ri ok
|
ELE13-03477
| Rough-In Permanent Service | 3/5/2014 | 3/5/2014 | 3/5/2014 3:07:01 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni called, told contractor that shall use ground bushings between meter base and meter can, and provide water tight connections for raceway
|
ELE14-00527
| Temporary Service | 3/5/2014 | 3/5/2014 | 3/5/2014 2:41:45 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00529
| Temporary Service | 3/5/2014 | 3/5/2014 | 3/5/2014 1:59:37 PM | P | PASS |
|
|
thanks! Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00528
| Temporary Service | 3/5/2014 | 3/5/2014 | 3/5/2014 1:22:17 PM | P | PASS |
|
|
Thanks! Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00526
| Temporary Service | 3/5/2014 | 3/5/2014 | 3/5/2014 12:58:44 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-00347
| Rough-In Permanent Service | 3/3/2014 | 3/5/2014 | 3/5/2014 12:31:31 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
|
ELE14-00520
| Rough-In Permanent Service | 3/4/2014 | 3/5/2014 | 3/5/2014 10:10:44 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson ri ok, p/s u/g n ok
|
ELE14-00514
| Temporary Service | 3/4/2014 | 3/5/2014 | 3/5/2014 9:32:35 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00492
| Temporary Service | 3/4/2014 | 3/5/2014 | 3/5/2014 9:26:40 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE13-02968
| Final | 3/4/2014 | 3/5/2014 | 3/5/2014 9:11:37 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni ok final
|
ELE13-03384
| Final | 3/4/2014 | 3/5/2014 | 3/5/2014 8:22:20 AM | A | FAIL |
|
|
Call for access Phone #: ###-#### >> Inspection requested via web by John VanZandt called, left correction notice, NEC 210.8(A) shall provide gfci for receptacles in garage and within 6' of sink, 250.94 shall install intersystem bond bar, 410.16(C) shall provide minimum 6" clearance from edge of closet shelf and edge of fluorescent luminaire
|