Inspections for the day of: Wednesday, March 5, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01275 ELE-Aging Inspection3/5/20143/5/20143/7/2014 3:00:18 PM DONE
called, contractor will check for final
ELE14-00451 Electrical Rough-In3/5/20143/5/20143/5/2014 3:08:31 PMPPART
Phone #: ###-#### >> Inspection requested via web by Eric Brown ri ok
ELE13-03477 Rough-In Permanent Service3/5/20143/5/20143/5/2014 3:07:01 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni called, told contractor that shall use ground bushings between meter base and meter can, and provide water tight connections for raceway
ELE14-00527 Temporary Service3/5/20143/5/20143/5/2014 2:41:45 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE14-00529 Temporary Service3/5/20143/5/20143/5/2014 1:59:37 PMPPASS
thanks! Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE14-00528 Temporary Service3/5/20143/5/20143/5/2014 1:22:17 PMPPASS
Thanks! Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE14-00526 Temporary Service3/5/20143/5/20143/5/2014 12:58:44 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE14-00347 Rough-In Permanent Service3/3/20143/5/20143/5/2014 12:31:31 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
ELE14-00520 Rough-In Permanent Service3/4/20143/5/20143/5/2014 10:10:44 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson ri ok, p/s u/g n ok
ELE14-00514 Temporary Service3/4/20143/5/20143/5/2014 9:32:35 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE14-00492 Temporary Service3/4/20143/5/20143/5/2014 9:26:40 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE13-02968 Final3/4/20143/5/20143/5/2014 9:11:37 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni ok final
ELE13-03384 Final3/4/20143/5/20143/5/2014 8:22:20 AMAFAIL
Call for access Phone #: ###-#### >> Inspection requested via web by John VanZandt called, left correction notice, NEC 210.8(A) shall provide gfci for receptacles in garage and within 6' of sink, 250.94 shall install intersystem bond bar, 410.16(C) shall provide minimum 6" clearance from edge of closet shelf and edge of fluorescent luminaire