FIR18-00077
| INSP-Sprinkler Rough-in | 3/5/2018 | 3/5/2018 | 3/5/2018 4:21:19 PM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
|
FIR18-00157
| INSP-Final Inspection | 3/1/2018 | 3/5/2018 | 3/5/2018 3:53:12 PM | P | PASS |
|
|
Final inspection for hood suppression system complete.
|
FIR16-00762
| INSP-Final Inspection | 3/5/2018 | 3/5/2018 | 3/5/2018 1:40:30 PM | P | PASS |
|
|
Final fire alarm inspection complete.
|
FIR16-00761
| INSP-Final Inspection | 3/5/2018 | 3/5/2018 | 3/5/2018 1:40:14 PM | P | PASS |
|
|
Final fire alarm inspection complete.
|
FIR16-00762
| INSP-Alarm Testing | 3/1/2018 | 3/5/2018 | 3/5/2018 1:39:37 PM | P | DONE |
|
|
Fire alarm testing complete.
|
FIR16-00761
| INSP-Alarm Testing | 3/1/2018 | 3/5/2018 | 3/5/2018 1:39:07 PM | P | DONE |
|
|
Fire alarm testing complete.
|
FIR16-00697
| INSP-Final Inspection | 3/1/2018 | 3/5/2018 | 3/5/2018 1:37:40 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
|
FIR16-00696
| INSP-Final Inspection | 3/1/2018 | 3/5/2018 | 3/5/2018 1:37:12 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
|
FIR17-00700
| INSP-Sprinkler Rough-in | 3/5/2018 | 3/5/2018 | 3/5/2018 11:50:35 AM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping/tenting on level 2 complete, level 2 approved for cover.
|
FIR18-00138
| INSP-Sprinkler Rough-in | 3/5/2018 | 3/5/2018 | 3/5/2018 10:46:00 AM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler located on level 1, southwest side new corridor complete, approved for cover.
|
FIR17-00047
| INSP-Final Inspection | 3/2/2018 | 3/5/2018 | 3/5/2018 10:31:22 AM | P | FAIL |
|
|
Replace painted fire sprinkler heads. Fire sprinkler head under stair landing on bottom level needs to be raised. Provide fire sprinkler in small hallway going to pantry from kitchen as shown on approved drawings. Fire sprinkler head in south bedroom is 24 inches away from center of ceiling fan, a minimum of 36 inches from center is required. Provide means of irrigation isolation when flow switch activates.
|
FIR18-00033
| INSP-Final Inspection | 3/5/2018 | 3/5/2018 | 3/5/2018 10:24:56 AM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
BLD18-00654
| FIRE-Final Inspection | 3/1/2018 | 3/5/2018 | 3/5/2018 10:24:16 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for this permit complete.
|
FIR18-00060
| INSP-Sprinkler Rough-in | 3/2/2018 | 3/5/2018 | 3/5/2018 8:55:04 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover.
|