Inspections for the day of: Monday, March 5, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00077 INSP-Sprinkler Rough-in3/5/20183/5/20183/5/2018 4:21:19 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR18-00157 INSP-Final Inspection3/1/20183/5/20183/5/2018 3:53:12 PMPPASS
Final inspection for hood suppression system complete.
FIR16-00762 INSP-Final Inspection3/5/20183/5/20183/5/2018 1:40:30 PMPPASS
Final fire alarm inspection complete.
FIR16-00761 INSP-Final Inspection3/5/20183/5/20183/5/2018 1:40:14 PMPPASS
Final fire alarm inspection complete.
FIR16-00762 INSP-Alarm Testing3/1/20183/5/20183/5/2018 1:39:37 PMPDONE
Fire alarm testing complete.
FIR16-00761 INSP-Alarm Testing3/1/20183/5/20183/5/2018 1:39:07 PMPDONE
Fire alarm testing complete.
FIR16-00697 INSP-Final Inspection3/1/20183/5/20183/5/2018 1:37:40 PMPPASS
Final fire sprinkler inspection complete.
FIR16-00696 INSP-Final Inspection3/1/20183/5/20183/5/2018 1:37:12 PMPPASS
Final fire sprinkler inspection complete.
FIR17-00700 INSP-Sprinkler Rough-in3/5/20183/5/20183/5/2018 11:50:35 AMPPART
Rough to cover inspection for overhead fire sprinkler piping/tenting on level 2 complete, level 2 approved for cover.
FIR18-00138 INSP-Sprinkler Rough-in3/5/20183/5/20183/5/2018 10:46:00 AMPPART
Rough to cover inspection for overhead fire sprinkler located on level 1, southwest side new corridor complete, approved for cover.
FIR17-00047 INSP-Final Inspection3/2/20183/5/20183/5/2018 10:31:22 AMPFAIL
Replace painted fire sprinkler heads. Fire sprinkler head under stair landing on bottom level needs to be raised. Provide fire sprinkler in small hallway going to pantry from kitchen as shown on approved drawings. Fire sprinkler head in south bedroom is 24 inches away from center of ceiling fan, a minimum of 36 inches from center is required. Provide means of irrigation isolation when flow switch activates.
FIR18-00033 INSP-Final Inspection3/5/20183/5/20183/5/2018 10:24:56 AMPPASS
Final fire sprinkler inspection for area of work complete.
BLD18-00654 FIRE-Final Inspection3/1/20183/5/20183/5/2018 10:24:16 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for this permit complete.
FIR18-00060 INSP-Sprinkler Rough-in3/2/20183/5/20183/5/2018 8:55:04 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover.