Inspections for the day of: Tuesday, March 5, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00946 INSP-Final Inspection3/4/20193/5/20193/6/2019 9:43:13 AMPFAIL
Tested 100% panel functionality. Sprinkler monitoring, initiaing and notification devices. Passed test. Still need updated addresses on as-built plans and building map, AC breaker lock. There was mention of access control being added before buillding is completed. Basement has a kitchen with residential hood. Class one hood may need to be added.

Please call Nate roughly 15 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by jason petty
NAF19-00011 INSP-Sprinkler Rough-in3/5/20193/5/20193/5/2019 3:19:46 PMPPASS
Rough-in passed. Piping can be covered. One dry pendant is overspaced on the west end of the north side exterior soffit.


As late as possible Phone #: 2083621888 >> Inspection requested via mobile web by Dan Buccino
FIR19-00103 INSP-Sprinkler Rough-in3/5/20193/5/20193/5/2019 1:43:40 PMPFAIL
Project is not ready yet for a complete rough-in inspection due to many missing heads in closets, balcony/storage closets, breezwway coverage, missing insulation for tenting. Also I noted that the breezeway has a soffit that may obstruct the sidewall sprinkler coverage.

Gabe Garduno is the contact. Thank you for all the help you give! Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-03757 FIRE-Final Inspection3/4/20193/5/20193/5/2019 1:30:22 PMPPASS
Life safety passed

KARL Phone #: ###-####
BLD18-03106 FIRE-Final Inspection3/4/20193/5/20193/5/2019 10:45:45 AMAFAIL
See the city approved notes for items marked that need corrected. Items included exhaust clearance from hvac intake, 3' housekeeping clearance, signage, class 1 electrical and ventilation interlock.....ect.


Plans are on-site. Ask for Stacie at the front desk. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
FIR19-00090 INSP-Sprinkler Rough-in3/4/20193/5/20193/5/2019 10:45:45 AMAPASS
Rough-in passed. Piping can be covered. Adam Phone #: ###-####
BLD18-03558 FIRE-Final Inspection3/4/20193/5/20193/5/2019 9:31:49 AMAPASS
Life safety passed

Jack Phone #: ###-####
BLD18-04186 FIRE-Final Inspection3/4/20193/5/20193/5/2019 8:26:43 AMAPASS
Life safety passed


Contact Jim Hibbard Phone #: ###-#### Inspection requested via web by James Hibbard
BLD19-00405 FIRE-Final Inspection3/4/20193/5/20193/5/2019 8:26:08 AMAPASS
Life safety passed

contact Jim Hibbard Phone #: ###-#### Inspection requested via web by James Hibbard
FIR19-00109 INSP-Final Inspection3/4/20193/5/20193/5/2019 7:52:43 AMAPASS
Permit finaled

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR19-00142 INSP-Final Inspection3/4/20193/5/20193/5/2019 7:51:11 AMAPASS
Permit finaled

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00139 INSP-Sprinkler Rough-in3/4/20193/5/20193/5/2019 12:00:00 AMPCANC
Mike Phone #: ###-####
FIR18-00740 INSP-Sprinkler Rough-in/Hydro3/4/20193/5/20193/4/2019 9:24:45 AMACANC
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Monday, March 04, 2019.