FIR18-00946
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/6/2019 9:43:13 AM | P | FAIL |
|
|
Tested 100% panel functionality. Sprinkler monitoring, initiaing and notification devices. Passed test. Still need updated addresses on as-built plans and building map, AC breaker lock. There was mention of access control being added before buillding is completed. Basement has a kitchen with residential hood. Class one hood may need to be added.
Please call Nate roughly 15 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by jason petty
|
NAF19-00011
| INSP-Sprinkler Rough-in | 3/5/2019 | 3/5/2019 | 3/5/2019 3:19:46 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered. One dry pendant is overspaced on the west end of the north side exterior soffit.
As late as possible Phone #: 2083621888 >> Inspection requested via mobile web by Dan Buccino
|
FIR19-00103
| INSP-Sprinkler Rough-in | 3/5/2019 | 3/5/2019 | 3/5/2019 1:43:40 PM | P | FAIL |
|
|
Project is not ready yet for a complete rough-in inspection due to many missing heads in closets, balcony/storage closets, breezwway coverage, missing insulation for tenting. Also I noted that the breezeway has a soffit that may obstruct the sidewall sprinkler coverage.
Gabe Garduno is the contact. Thank you for all the help you give! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-03757
| FIRE-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 1:30:22 PM | P | PASS |
|
|
Life safety passed
KARL Phone #: ###-####
|
BLD18-03106
| FIRE-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 10:45:45 AM | A | FAIL |
|
|
See the city approved notes for items marked that need corrected. Items included exhaust clearance from hvac intake, 3' housekeeping clearance, signage, class 1 electrical and ventilation interlock.....ect.
Plans are on-site. Ask for Stacie at the front desk. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
|
FIR19-00090
| INSP-Sprinkler Rough-in | 3/4/2019 | 3/5/2019 | 3/5/2019 10:45:45 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered. Adam Phone #: ###-####
|
BLD18-03558
| FIRE-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 9:31:49 AM | A | PASS |
|
|
Life safety passed
Jack Phone #: ###-####
|
BLD18-04186
| FIRE-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 8:26:43 AM | A | PASS |
|
|
Life safety passed
Contact Jim Hibbard Phone #: ###-#### Inspection requested via web by James Hibbard
|
BLD19-00405
| FIRE-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 8:26:08 AM | A | PASS |
|
|
Life safety passed
contact Jim Hibbard Phone #: ###-#### Inspection requested via web by James Hibbard
|
FIR19-00109
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 7:52:43 AM | A | PASS |
|
|
Permit finaled
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR19-00142
| INSP-Final Inspection | 3/4/2019 | 3/5/2019 | 3/5/2019 7:51:11 AM | A | PASS |
|
|
Permit finaled
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00139
| INSP-Sprinkler Rough-in | 3/4/2019 | 3/5/2019 | 3/5/2019 12:00:00 AM | P | CANC |
|
|
Mike Phone #: ###-####
|
FIR18-00740
| INSP-Sprinkler Rough-in/Hydro | 3/4/2019 | 3/5/2019 | 3/4/2019 9:24:45 AM | A | CANC |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Monday, March 04, 2019.
|