ELE19-00602 Final3/5/20203/5/20203/5/2020 3:20:56 PMPFAIL
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 110.3(B)- Exit lights shall have an operating temp for the environment for which it is installed. 0 degrees celcius to 50 degrees celcius,
32 degrees F to 104 degrees F installed.
-40 degrees C to 50 degrees C on order.
110.26(D)- Illumination around electrical service and panel boards shall not be controlled by automatic means.
Fire alarm circuit breaker is located in a hotel electrical room which is under construction, illumination required.
ELE20-00708 Electrical Rough-In3/5/20203/5/20203/5/2020 2:32:26 PMPPASS
walls and hard ceilings, call Art with access info 2088711608 Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Next trip request Sean Gafford phone number for escort to respect privacy people inside.
Offices at various locations wall rough in ok cover.
ELE20-00709 Temporary Service3/4/20203/5/20203/5/2020 10:52:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-02188 Electrical Rough-In3/4/20203/5/20203/5/2020 10:03:55 AMAFAIL
rough in for breezeway furred down ceiling areas.
Contact Ben for locations. ###-####
Rough in for heat tape home run. Phone #: ###-#### Inspection requested via web by Todd Hall
Wrong permit and address.
ELE20-00774 Electrical Rough-In3/4/20203/5/20203/5/2020 9:51:39 AMAPASS
Matt is the builder call for access after 9AM Phone #: ###-#### Inspection requested via web by David Green
Addition for utility, master bath, closet, office and smokes rough in ok cover
ELE20-00778 Electrical Rough-In3/5/20203/5/20203/5/2020 9:33:17 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Store manager helped locate area to coolers located between deli and back south west corner of store, no discription of work performed, No Building permit attached to electrical permit. Stamped set of prints on site, no access to area above to verify disconnecting means, listings confirmed with cooler assembly.
Must attach to building permit, must meet on site and provide access to disconnecting means above coolers as noted on print.