Inspections for the day of: Monday, March 6, 2006.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03391 ELE-Aging Inspection3/6/20063/6/20063/7/2006 8:51:19 AM NR
suc
ELE06-00766 Electrical Rough-In3/6/20063/6/20063/6/2006 4:03:00 PMPPART
John; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
walls ok
ELE06-00747 Electrical Rough-In3/6/20063/6/20063/6/2006 3:35:21 PMPPART
Lloyd -- for Suite 102 wall cover approval; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
walls ok
ELE05-04070 Final3/6/20063/6/20063/6/2006 1:45:39 PMPNR
peter ###-####
I posted stop work.
wires run to the garage without a permit or inspection. this was not done by joe.
the inspection was not called for by the electrical contractor. no final has been done yet.
ELE05-02624 Final3/6/20063/6/20063/6/2006 1:42:32 PMPPASS
###-#### Peter
ELE06-00723 Rough-In Permanent Service3/6/20063/6/20063/6/2006 1:02:29 PMPPART
###-####. Scheduled by a contractor via Hello! on 3/6/2006 at 9:22:48 AM. Contact: ###-####.
R/I Ok
electrode not yet in concrete
ELE05-04132 Electrical Rough-In3/3/20063/6/20063/6/2006 10:48:12 AMAPART
Dan -- wall ; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
hard lids ok
ELE05-02649 Final3/2/20063/6/20063/6/2006 10:21:41 AMAFAIL
Darren; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
the door-bell transformer behind the refridgerator has exposed 120 volt wires and low vlotage wires in a box and comming through a bare hole to the transformer that is mounted on the wall above the box.
ELE05-04355 Final3/3/20063/6/20063/6/2006 9:58:25 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tina Payne
ELE05-04566 Final3/3/20063/6/20063/6/2006 8:40:12 AMANH
We installed a new j-box in the existing conduit between the indoor panel and the outdoor panel and replaced the wires in this run because the roofers cut the conduit(who knows WHAT they were thinking!!!!). We also installed a new disconnect for the AC. The AC was connected by others. We also installed a new GFCI weather proof receptacle beside the AC.(#5121347hampikian). Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
no access
ELE05-04575 Final3/3/20063/6/20063/6/2006 8:39:28 AMAFAIL
final inspection on kitchen remodel call Tom @###-#### so he can let you in. Internet Inspection Request from: Andy Rose
13 in counter has no recep.
210.52(C) Countertops.
Kitchen GFCI recep.
200.11 Polarity of Connections.

ELE05-02624 DOC - Permit Expired3/6/20063/6/20063/6/2006 12:00:00 AMPPASS
###-#### Peter
this job was taken over by E-Zee electric Permit # ELE05-05070
ELE05-03326 DOC - Permit Expired3/6/20063/6/20063/6/2006 12:00:00 AMPPASS
no electric in the sign