Inspections for the day of: Tuesday, March 6, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00730 Permanent Service3/6/20073/6/20073/7/2007 6:29:14 AMPNR
brenda Note: storage shed will be relocated from pole for clearance; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contr, no grounding done,shed in way, still making up service, no mis permit for trailer, ipco called late pm, 370 said ok to install meter as tenant would not have power overnight, but called to have contr recall for inspection, and said that possible to pull meter if violations remain. Contr called later and said that park had crew to move shed on Wednesday, and they will find out about MIS for tie-downs.
ELE06-00680 ELE-Aging Inspection3/6/20073/6/20073/6/2007 3:50:24 PM DONE
ok to final, see final
ELE06-00680 Final3/6/20073/6/20073/6/2007 3:49:18 PMPPASS
ok to final
ELE07-00623 Conference3/6/20073/6/20073/6/2007 3:48:23 PMPDONE
Would like to conference about the grounding issues for this loction and project. Phone #: ###-#### talked about gec and grounding 2nd point of service
ELE06-01478 Electrical Rough-In3/6/20073/6/20073/6/2007 2:54:53 PMPPASS
pole base ins. on parking lot lights Phone #: ###-#### u/g already done, called and said pole base grounding shall be per spec or design, we look at as branch circuits at final
ELE07-00731 Permanent Service3/6/20073/6/20073/6/2007 2:23:45 PMPNR
brenda .; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contr, supposed to be later
ELE07-00732 Permanent Service3/6/20073/6/20073/6/2007 2:23:02 PMPNR
brenda - ###-#### met contr, supposed to be tomorrow
ELE07-00726 Temporary Service3/6/20073/6/20073/6/2007 1:36:32 PMPFAIL
brandon ###-#### called contr, left corr notice, nec 110.26(A)(1)work space shall be provided about elect equipment-depth
ELE07-00682 Electrical Rough-In3/5/20073/6/20073/6/2007 1:12:03 PMPPASS
Requesting an inspection to cover. Phone #: ###-#### walls and hard lids ok to cover only, told elect pull box not allowed under foreign piping
ELE07-00516 Final3/6/20073/6/20073/6/2007 12:34:45 PMPPASS
9411713 ok to final, no card to sign
ELE07-00098 Final3/6/20073/6/20073/6/2007 12:20:04 PMPPASS
Lynn; Phone #: ###-#### Internet Inspection Request from: Stacie Backus

For both units ok to final, signed occ card
ELE07-00693 Electrical Rough-In3/6/20073/6/20073/6/2007 10:22:55 AMPPART
joe ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover lower rear soffit only
ELE07-00712 Temporary Service3/5/20073/6/20073/6/2007 10:14:19 AMAPASS
ron; Phone #: ###-#### Internet Inspection Request from: Victoria Beall t/s u/g n ok
ELE07-00704 Electrical Rough-In3/5/20073/6/20073/6/2007 10:00:42 AMAFAIL
Scheduled by a contractor via Hello! on 3/5/2007 at 4:55:32 PM. Contact: ###-####. called, left message, nec 250.92 (A)(3) metallic raceway enclosing gec shall be bonded at each end, 250.53(C)(2) water system shall be supplemented by electrodes and bonded to grounded service conductor, 250.70 listed and approved connections shall be used for gec, 352.30(A) rnc shall be securely fastened within 3' of termination, 314.17(C) nm cable shall be secured within 8"of box, 210.52(A)(2) wall spaces over 2' shall have recpt installed, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 210.52(E) shall provide outlet at front of dwelling, 110.26(F)(1)(a) there shall be no foreign piping systems over equipment, 110.12(A) there shall be no broken parts (boxes), 300.14 at least 6" of free conductor shall be in each box, Bcc all make-up shall be done, grounds together, Reserved right to amend corr notice, left do not cover sticker
ELE07-00009 Final3/5/20073/6/20073/6/2007 8:33:45 AMAPASS
alan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE07-00182 Final3/5/20073/6/20073/6/2007 7:53:05 AMAPASS
Scheduled by a contractor via Hello! on 3/5/2007 at 9:20:25 PM. Contact: ###-####. ok to final, signed occ card