FIR07-01000
| INSP-Final Inspection | 3/5/2008 | 3/6/2008 | 3/7/2008 10:48:55 AM | P | FAIL |
|
|
Site inspection comments per K.Roule
Tested FA monitoring of VT and waterflow (by manual means). Both annunciated correctly at panel and offsite monitoring station. Visually observed location of dry sidewall sprinkler installed in exterior chimney. Work remaining on this permit:
1. Test the new fire alarm monitoring module which was installed on the existing cooking hood suppression system under this permit. (Requires the hood fire suppression system contractor to be present)
2. Test the waterflow alarm switch by flowing water from the test connection. (Requires the sprinkler contractor responsible for FIR04-00490 be present).
3. Provide fire alarm-initiated interlocks which shut off the hood exhaust fan and the gas fuel to the cooking appliances, as specified in the signed Fire Department Agreement dated 2/4/2004 and in F.Varley's letter dated 4 Feb 2002 letter (Item 2).
4. Correct the existing "trouble" condition on the fire alarm panel.
5. Provide an updated alarm map reflecting the current floor plan and all initiating device locations correlated with the annunciated fire alarm device addresses. (NFPA 72 4.4.6.1).
6. Replace the missing door latch on the FACP cabinet and update the outdated monitoring company and account information currently posted inside the cabinet.
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 3/5/2008 | 3/6/2008 | 3/6/2008 5:08:24 PM | P | PART |
|
|
Inspection for the seismic upgrade areas at the plaza level to be completed in conjunction with the hydrostatic test for this level per agreement.
|
BLD06-03315
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 5:02:30 PM | P | PASS |
|
|
Fire life safety is satisfactory.
|
BLD06-03316
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 5:01:58 PM | P | PASS |
|
|
Fire life safety is satisfactory.
|
BLD06-03311
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 5:01:09 PM | P | PASS |
|
|
Fire life safety completed acceptable.
|
BLD06-03310
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 5:00:28 PM | P | PASS |
|
|
Fire life safety completed acceptable.
|
BLD06-03306
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 4:59:38 PM | P | PASS |
|
|
Fire life safety completed acceptable.
|
BLD06-03519
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 4:58:50 PM | P | PASS |
|
|
Fire life safety passed.
|
BLD06-03522
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 4:58:05 PM | P | PASS |
|
|
Fire life safety passed.
|
BLD06-03523
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 4:57:20 PM | P | PASS |
|
|
Fire life safety finaled.
|
BLD06-03524
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 4:56:48 PM | P | PASS |
|
|
Fire life safety finaled.
|
BLD06-03526
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 4:55:45 PM | P | NR |
|
|
Project job site is not in condition for final fire life safety approval.
|
FIR08-00080
| INSP-Sprinkler Rough-in | 3/6/2008 | 3/6/2008 | 3/6/2008 4:52:28 PM | P | PART |
|
|
OH sprinkler rough-in is approved for cover at the drop ceiling areas within the tenant remodel area.
|
BLD07-02081
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 2:41:39 PM | P | FAIL |
|
|
Missing doors and hardware at both restrooms, need to provide and post one PFE for each level per fire code review notes, provide building address as discussed facing 10th street.
|
BLD06-03305
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 12:57:53 PM | P | NR |
|
|
Project is not in condition for final at this time due to construction underway, finishes not complete, missing door hardware, etc.
|
BLD06-03521
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 12:55:58 PM | P | FAIL |
|
|
Missing smoke seal at the back exit, need to adjust the closure at the trash chute door in the common corridor.
|
BLD06-03520
| FIRE-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 12:54:13 PM | P | FAIL |
|
|
Missing escutcheon at the master bath, provide smoke seal at the back exit door.
|
FIR07-00324
| INSP-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 12:51:55 PM | A | NR |
|
|
In duct detectors and general alarm notification devices tested okay, final pending testing of single station smoke alarms when project is in condition for final.
|
FIR07-00648
| INSP-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 12:48:33 PM | A | PASS |
|
|
Final fire alarm testing passed, permit finaled.
|
FIR07-00466
| INSP-Final Inspection | 3/6/2008 | 3/6/2008 | 3/6/2008 12:47:35 PM | A | PASS |
|
|
Final fire alarm testing completed satisfactory, permit finaled.
|
BLD07-03159
| FIRE-Final Inspection | 3/5/2008 | 3/6/2008 | 3/6/2008 11:23:04 AM | A | PASS |
|
|
Fire life safety inspection completed acceptable, suite address numbers to be posted at the common corridor as discussed.
|
BLD07-03158
| FIRE-Final Inspection | 3/5/2008 | 3/6/2008 | 3/6/2008 11:21:21 AM | A | PASS |
|
|
Fire life safety finaled.
|
BLD07-03157
| FIRE-Final Inspection | 3/5/2008 | 3/6/2008 | 3/6/2008 11:20:36 AM | A | PASS |
|
|
Fire life safety final inspection passed.
|