ELE13-00384
| Final | 3/6/2013 | 3/6/2013 | 3/6/2013 2:25:00 PM | P | PASS |
|
|
Edwin Phone #: ###-#### ok final
|
ELE13-00462
| Rough-In Permanent Service | 3/6/2013 | 3/6/2013 | 3/6/2013 2:07:27 PM | P | PASS |
|
|
office Phone #: ###-#### ri ok, p/s u/g n ok
|
ELE12-02685
| Conference | 3/5/2013 | 3/6/2013 | 3/6/2013 1:17:48 PM | P | DONE |
|
|
Please call Darin with any questions Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni talked about labelling and listing for control panel, skids, and installation for pole bases, seal-offs appear to be ok
|
ELE13-00169
| Final | 3/6/2013 | 3/6/2013 | 3/6/2013 12:33:36 PM | P | PASS |
|
|
homeowner is home Phone #: ###-#### >> Inspection requested via web by Julie Schroder ok final
|
ELE13-00504
| Temporary Service | 3/6/2013 | 3/6/2013 | 3/6/2013 11:51:49 AM | P | FAIL |
|
|
Steve Phone #: ###-#### called, no job id sticker, no address, no esc sign,NEC 408..4 shall label breakers, NEC 230.42(B) shall provide proper ampacity service conductors
|
ELE13-00503
| Permanent Service | 3/6/2013 | 3/6/2013 | 3/6/2013 10:56:24 AM | P | FAIL |
|
|
We Would Like To Get A Perm Service And Power Swing. Also We Would Like A Consult On This Project So could You Please Call Me When You Are Heading That Way! Thanks So Much Dave Phone #: ###-#### >> Inspection requested via web by jason shifflett shall provide proper sized pull box at service per NEC 314
|
ESC13-00018
| General Inspection | 3/6/2013 | 3/6/2013 | 3/6/2013 10:07:37 AM | | PASS |
|
|
looked done, no sign, cleaned up
|
ELE13-00358
| Electrical Rough-In | 3/5/2013 | 3/6/2013 | 3/6/2013 9:43:15 AM | A | PART |
|
|
Underground Inspection - contact is Phil Keetch - ###-#### Phone #: ###-#### >> Inspection requested via web by Scott Campbell west part field 1 u/g ok cover
|
ELE13-00485
| Temporary Service | 3/5/2013 | 3/6/2013 | 3/6/2013 8:59:31 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn corrections made, t/s u/g n ok
|
ELE13-00492
| Rough-In Permanent Service | 3/6/2013 | 3/6/2013 | 3/6/2013 8:30:24 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, told contractor about installing expansion joint in riser per IPCO, ri ok, p/s u/g n ok
|
ELE13-00275
| Final | 3/6/2013 | 3/6/2013 | 3/6/2013 7:49:19 AM | A | PASS |
|
|
Jeff ###-#### ok final, no card
|