Inspections for the day of: Wednesday, March 6, 2013.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00698 INSP-Alarm Testing3/5/20133/6/20133/7/2013 12:11:43 PMPPART
Functional testing and inspection for fire alarm work in "phase one" completed. Noted items include; provide a WP notification appliance in the decontamination room, address at SD's for door release (22 &23) are switched, SD and ID at the south set of hallway doors between phase one and two are not yet installed, ID M8-13 has been relocated to the main corridor beyond phase one, delayed egress provisions at the secured doors must meet conditions per IFC 2009, record drawings and panel maps to match field modifications including device locations and addressing. Chimes/strobes, MP at the nurses station, SD and ID(except as noted) tested okay. *Inspection completed 3/6/13 PM*.
FIR12-00691 INSP-Final Inspection3/5/20133/6/20133/7/2013 11:48:55 AMPPART
Fire sprinkler work at "phase one" completed and passed walkthrough inspection.
BLD12-02108 FIRE-Final Inspection3/6/20133/6/20133/7/2013 11:06:16 AMPPASS
Fire life safety finaled.
FIR12-00679 INSP-Final Inspection3/6/20133/6/20133/7/2013 11:05:16 AMPPASS
Fire sprinkler permit finaled.
FIR13-00060 INSP-Final Inspection3/5/20133/6/20133/7/2013 11:03:37 AMPPASS
Fire alarm work passed inspection and testing- flow switch repaired while on site-. Permit finaled.
FIR12-00679 INSP-Supply line flush3/6/20133/6/20133/7/2013 11:00:34 AMPPART
UG fire supply line flush completed satisfactory.
BLD13-00372 FIRE-Final Inspection3/5/20133/6/20133/6/2013 2:50:04 PMPFAIL
Post "door to remain.." signage at the main entry/exit, post PFE at 48" max. AFF, remove surface bolts and security grate with hasp at both warehouse exits, provide permit documents with the correct address, provide verification of a current annual inspection for the existing fire sprinkler system.
BLD12-00863 FIRE-Final Inspection3/6/20133/6/20133/6/2013 2:14:09 PMPPASS
Life safety passed pending manual thumbturn at the exit door is removed- to be corrected prior to structural final inspection for verification at that time per agreement with contractor.
BLD13-00124 FIRE-Final Inspection3/6/20133/6/20133/6/2013 2:10:07 PMPPASS
Verified approved plan resubmittal. Fire life safety finaled.
FIR12-00723 INSP-Sprinkler Rough-in3/4/20133/6/20133/6/2013 1:01:23 PMAPART
Rough-in at the second floor completed. Discussed shell/TI schedule, hydrostatic test procedures, floor control manifold/PRV isolation valves per the mfg. data sheets and approved plans.
FIR12-00328 INSP-Final Inspection3/5/20133/6/20133/6/2013 12:57:27 PMAPASS
Previous inspection items okayed, recieved record of completion documents. Fire alarm permit finaled.
FIR12-00327 INSP-Final Inspection3/5/20133/6/20133/6/2013 12:53:57 PMAPASS
C/N items verified. Record of completion forms recieved. Fire alarm permit finaled.