Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00194 ELE-Aging Inspection3/6/20143/6/20143/7/2014 2:51:45 PM DONE
spoke with Robert and he says he'll call it in and he thinks hes ready
ELE12-01290 ELE-Aging Inspection3/6/20143/6/20143/7/2014 2:32:15 PM DONE
no phone number to call
ELE14-00533 Permanent Service3/5/20143/6/20143/6/2014 3:03:12 PMPPASS
If possible would like to inspect service. Then on Monday the entire home.
Please call 15 minutes prior so we can have it open for you. Phone #: ###-#### >> Inspection requested via web by Eddy Udry p/s o/h rec ok 1 meter for 2518 and 1 meter for 2520 are on site in old service being removed
ELE14-00185 Permanent Service3/6/20143/6/20143/6/2014 2:13:34 PMPPASS
IDPCO is fine with the clearance
I will have them labeled by noon
Thanks Brad Phone #: ###-#### >> Inspection requested via web by Brad Baker p/s o/h n ok 1-CT meter and 1-100 amp 3phase meter
ELE12-03105 Final3/5/20143/6/20143/6/2014 2:01:58 PMAFAIL
brent Phone #: ###-#### NEC 210.8(A)(7) receptacles installed within 6 feet of outside edge of sinks need to be GFI protected. bath and laundry room. NEC 210.12(B) all 120 volt 15 or 20 amp circuits supplying outlets in bedrooms shall be protected by a arc fault circuit interupter device. If someone other than homeowner is performing the electrical work, they need to pull a permit in their name.
ELE14-00307 Electrical Rough-In3/5/20143/6/20143/6/2014 1:28:52 PMAPASS
ron - ceiling Phone #: ###-#### north half of ceilings ok for cover. Contractor agrees to install some ko seals in existing boxes and support existing conduits at a few locations through out north ceiling before covering
ELE14-00185 Permanent Service3/5/20143/6/20143/6/2014 10:17:35 AMAFAIL
Please call with any questions Phone #: ###-#### >> Inspection requested via web by Brad Baker p/s o/h n ok Contractor needs to label meters with addresses and deal with working clearance 36" of level working platform in front of meters
ELE14-00370 Final3/4/20143/6/20143/6/2014 8:19:23 AMPCANC
Contact: Josh Mangum, please call 30 minutes before going. Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden