Inspections for the day of: Thursday, March 6, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00089 INSP-Sprinkler Rough-in3/5/20143/6/20143/6/2014 4:48:39 PMPPART
Fire sprinkler work at the front office areas passed inspection. Need to add hangers at three branchlines to new heads in the tool crib. Noted missing coverage below the overhead door at the tool storage bay north end of the building adjacent to the tool crib.
FIR13-00704 INSP-Sprinkler Rough-in3/6/20143/6/20143/6/2014 3:37:08 PMPPART
Overhead work at the grid ceiling areas completed to date okay for cover. Flex heads at some locations are not perpendicular to the ceiling and will need adjustment.
FIR14-00047 INSP-Final Inspection3/6/20143/6/20143/6/2014 3:30:22 PMPPASS
Verified additional coverage. Final walkthrough passed. Permit finaled.
BLD14-00410 FIRE-Final Inspection2/28/20143/6/20143/6/2014 10:41:30 AMAPASS
Life safety inspection completed. Remove or blank non-required exit sign at the south door or provide correct hardware.
FIR14-00037 INSP-Final Inspection3/5/20143/6/20143/6/2014 10:12:04 AMAPASS
Scope of fire alarm work passed field inspection and functional testing. Coverage adjustment at the conference room east side completed while on site. Permit finaled.