FIR14-00089
| INSP-Sprinkler Rough-in | 3/5/2014 | 3/6/2014 | 3/6/2014 4:48:39 PM | P | PART |
|
|
Fire sprinkler work at the front office areas passed inspection. Need to add hangers at three branchlines to new heads in the tool crib. Noted missing coverage below the overhead door at the tool storage bay north end of the building adjacent to the tool crib.
|
FIR13-00704
| INSP-Sprinkler Rough-in | 3/6/2014 | 3/6/2014 | 3/6/2014 3:37:08 PM | P | PART |
|
|
Overhead work at the grid ceiling areas completed to date okay for cover. Flex heads at some locations are not perpendicular to the ceiling and will need adjustment.
|
FIR14-00047
| INSP-Final Inspection | 3/6/2014 | 3/6/2014 | 3/6/2014 3:30:22 PM | P | PASS |
|
|
Verified additional coverage. Final walkthrough passed. Permit finaled.
|
BLD14-00410
| FIRE-Final Inspection | 2/28/2014 | 3/6/2014 | 3/6/2014 10:41:30 AM | A | PASS |
|
|
Life safety inspection completed. Remove or blank non-required exit sign at the south door or provide correct hardware.
|
FIR14-00037
| INSP-Final Inspection | 3/5/2014 | 3/6/2014 | 3/6/2014 10:12:04 AM | A | PASS |
|
|
Scope of fire alarm work passed field inspection and functional testing. Coverage adjustment at the conference room east side completed while on site. Permit finaled.
|