BLD14-00764
| FIRE-Final Inspection | 3/5/2015 | 3/6/2015 | 3/6/2015 2:35:57 PM | A | FAIL |
|
|
Items needed prior to final include; post missing fire extinguisher at location indicated per plan, new hydrant per plan sheet G1.0 is not yet installed. Refer to project fire code review notes for details.
|
FIR14-00430
| INSP-Sprinkler Rough-in | 3/4/2015 | 3/6/2015 | 3/6/2015 2:32:51 PM | A | PART |
|
|
Completed rough-in inspection for tower 3 podium level living units as noted on plans. Missing drops and sprinklers at unit 206 bedroom and closet, provide standard pendent heads per plan at both trash rooms, unit 215 is missing sprinkler coverage at a closet and need to relocate one head too close to a ceiling fan junction box. Discussed floor control manifold location and configurations.
|
BLD14-03544
| FIRE-Final Inspection | 3/5/2015 | 3/6/2015 | 3/6/2015 2:26:30 PM | A | FAIL |
|
|
Missing one exit sign per approved plans at the center hallway, provide approved style hardware at the second exit, post "door to remain...." signage at the main entry/exit, remove manual thumbturn and provide keyed lock as discussed at the main entry/exit, post fire extinguishers at locations per plan and discussion.
|