Inspections for the day of: Monday, March 6, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-02938 FIRE-Final Inspection3/6/20173/6/20173/6/2017 3:12:45 PMPFAIL
No plans or small documents on site. I did a courtesy walk through with Adam. I noted the need for fire sprinkler and fire alarm modifications in several locations. It appears the emergency generator has been removed so backup power for emergency lights is an issue. Door hardware does not meet ADA on the new doors.

Leanne Phone #: ###-####
FIR17-00013 INSP-Sprinkler Rough-in3/6/20173/6/20173/6/2017 3:09:53 PMPPASS
Rough-in passed. Tenting passed. Pendants modified for soffits in Kitchen. Piping can be covered.
FIR17-00009 INSP-Sprinkler Rough-in3/3/20173/6/20173/6/2017 3:08:56 PMAPASS
Tenting inspection passed and piping can be covered. Also pendant sprinkler modifications due to soffits in the Kitchen have been completed. Piping can be covered.
FIR17-00011 INSP-Sprinkler Rough-in3/3/20173/6/20173/6/2017 3:07:28 PMACANC
Johathon Phone #: ###-####
BLD17-00218 FIRE-Final Inspection3/3/20173/6/20173/6/2017 1:34:58 PMPFAIL
Provide annual inspection for the fire extinguishers
BLD17-00430 FIRE-Final Inspection3/3/20173/6/20173/6/2017 1:34:33 PMPFAIL
Provide address, annual inspection for fire extinguishers and repair or remove exit sign.
FIR16-00284 INSP-Sprinkler Rough-in3/3/20173/6/20173/6/2017 9:23:17 AMAPASS
Apartment 302 lower soffits ok to cover.