BLD16-02938
| FIRE-Final Inspection | 3/6/2017 | 3/6/2017 | 3/6/2017 3:12:45 PM | P | FAIL |
|
|
No plans or small documents on site. I did a courtesy walk through with Adam. I noted the need for fire sprinkler and fire alarm modifications in several locations. It appears the emergency generator has been removed so backup power for emergency lights is an issue. Door hardware does not meet ADA on the new doors.
Leanne Phone #: ###-####
|
FIR17-00013
| INSP-Sprinkler Rough-in | 3/6/2017 | 3/6/2017 | 3/6/2017 3:09:53 PM | P | PASS |
|
|
Rough-in passed. Tenting passed. Pendants modified for soffits in Kitchen. Piping can be covered.
|
FIR17-00009
| INSP-Sprinkler Rough-in | 3/3/2017 | 3/6/2017 | 3/6/2017 3:08:56 PM | A | PASS |
|
|
Tenting inspection passed and piping can be covered. Also pendant sprinkler modifications due to soffits in the Kitchen have been completed. Piping can be covered.
|
FIR17-00011
| INSP-Sprinkler Rough-in | 3/3/2017 | 3/6/2017 | 3/6/2017 3:07:28 PM | A | CANC |
|
|
Johathon Phone #: ###-####
|
BLD17-00218
| FIRE-Final Inspection | 3/3/2017 | 3/6/2017 | 3/6/2017 1:34:58 PM | P | FAIL |
|
|
Provide annual inspection for the fire extinguishers
|
BLD17-00430
| FIRE-Final Inspection | 3/3/2017 | 3/6/2017 | 3/6/2017 1:34:33 PM | P | FAIL |
|
|
Provide address, annual inspection for fire extinguishers and repair or remove exit sign.
|
FIR16-00284
| INSP-Sprinkler Rough-in | 3/3/2017 | 3/6/2017 | 3/6/2017 9:23:17 AM | A | PASS |
|
|
Apartment 302 lower soffits ok to cover.
|