FIR16-00606
| INSP-Sprinkler Rough-in | 3/6/2017 | 3/6/2017 | 3/6/2017 3:21:48 PM | P | PART |
|
|
Partial rough in inspection for overhead fire sprinkler piping located on level 5 complete, notated plans that were on site with yellow highlighter/red ink, area's that were inspected. Need to have a city approved set of drawings on site for next inspection. Piping in attic spaces cannot be covered until tenting is installed, inspected and passed, any piping that is covered before tenting inspection will have cover material removed to verify tenting installation.
|
BLD17-00429
| FIRE-Final Inspection | 3/6/2017 | 3/6/2017 | 3/6/2017 11:26:34 AM | P | FAIL |
|
|
Exit signs on south side exit doors need to be serviced. Two escutcheons missing on fire sprinkler heads on the east side of tenant space. Tenant space has no fire extinguishers, extinguishers need to be installed. Addressing needs to be updated, tenant space has two addresses, 1099 and 1081, permit has 1081 for tenant addressing.
|
FIR17-00091
| INSP-Final Inspection | 3/3/2017 | 3/6/2017 | 3/6/2017 10:36:32 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|