BLD19-00569
| FIRE-Final Inspection | 3/6/2019 | 3/6/2019 | 3/6/2019 2:13:12 PM | P | PASS |
|
|
life safety passed
abdel Phone #: ###-####
|
NAF19-00011
| INSP-Sprinkler Rough-in | 3/5/2019 | 3/6/2019 | 3/6/2019 2:00:57 PM | A | CANC |
|
|
Call prior to going Phone #: 2083621888 >> Inspection requested via mobile web by Dan
|
FIR19-00165
| INSP-Final Inspection | 3/5/2019 | 3/6/2019 | 3/6/2019 1:42:52 PM | P | FAIL |
|
|
AES doesn't annunciate locally for troulbe. May need to change radio out. Verified signals. Reports correctly. final when piezo installed which may require a different radio (per mike) and would require a resubmittal. Final when piezo is resolved.
Please call Mike at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
|
FIR18-00204
| INSP-Final Inspection | 3/6/2019 | 3/6/2019 | 3/6/2019 1:42:52 PM | P | FAIL |
|
|
Alarmco's as-builts showed wrong panel. tested signal. panel trouble relay does not latch and resets when silenced. signals report. To final permit ad-builts needed.
call ahead // bill Phone #: ###-####
|
FIR18-00680
| INSP-Sprinkler Rough-in | 3/5/2019 | 3/6/2019 | 3/6/2019 12:03:15 PM | A | PASS |
|
|
Tenting has been repaired. Piping can be covered. Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD18-03979
| FIRE-Final Inspection | 3/5/2019 | 3/6/2019 | 3/6/2019 10:39:18 AM | A | PASS |
|
|
Life safety passed. No alarm or sprinkler work.
Please call ahead of time for inspection
Thanks Mike Teeter ###-#### Phone #: ###-#### Inspection requested via web by Mike Teeter
|
BLD19-00628
| FIRE-Final Inspection | 3/6/2019 | 3/6/2019 | 3/6/2019 10:37:21 AM | P | PASS |
|
|
life safety passed. Perm. suite numbers to be installed prior to a building final. Matt Phone #: ###-####
|
BLD19-00626
| FIRE-Final Inspection | 3/6/2019 | 3/6/2019 | 3/6/2019 10:37:06 AM | P | PASS |
|
|
life safety passed. Perm. suite numbers to be installed prior to a building final. Matt Phone #: ###-####
|
FIR18-00139
| INSP-Sprinkler Rough-in | 3/5/2019 | 3/6/2019 | 3/6/2019 9:49:56 AM | A | PASS |
|
|
Rough in passed. Fire alarm tie in passed. Apoproved for cover. Final can be signed off after ceiling tile is installed.
mike Phone #: ###-####
|
FIR18-00946
| INSP-Final Inspection | 3/6/2019 | 3/6/2019 | 3/6/2019 9:48:16 AM | A | FAIL |
|
|
Tested 100% panel functionality. Sprinkler monitoring, initiaing and notification devices. Passed test. Still need updated addresses on as-built plans and building map, AC breaker lock. There was mention of access control being added before buillding is completed. Basement has a kitchen with residential hood. Class one hood may need to be added.
Nate with Peak was on site.
|
BLD19-00626
| FIRE-Supply Line Hydro | 3/5/2019 | 3/6/2019 | 3/6/2019 12:00:00 AM | A | CANC |
|
|
Phone #: ###-####
|
NAF19-00011
| INSP-Sprinkler Rough-in | 3/4/2019 | 3/6/2019 | 3/5/2019 8:02:33 AM | A | CANC |
|
|
As early as possible Phone #: 7753857345 >> Inspection requested via mobile web by Roy Inspection cancelled via mobile web on Tuesday, March 05, 2019.
|