Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00808 Rough-in3/6/20193/6/20193/6/2019 3:33:21 PMPPASS
Call manny 20 min advance
Thanks Phone #: ###-#### Inspection requested via web by Manuel Canto
- R/I ok
- 20lb gas pressure test ok
MEC19-00925 Pressure Test3/5/20193/6/20193/6/2019 2:35:48 PMPPASS
Please call Chuck on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- 20lb gas pressure test ok to unit heater
MEC19-00925 Final3/5/20193/6/20193/6/2019 2:35:24 PMPCANC
Please call Chuck on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- unit heater will be finished when homeowner has roof done on shop. Roofing company wants to install the roof jack.
- schedule inspection when unit heater is finished
MEC19-00212 Final3/4/20193/6/20193/6/2019 1:42:52 PMPPASS
Call Jason @ ###-#### with any issues. Phone #: ###-#### Inspection requested via web by Angie Maguire
- final ok
MEC18-02559 Mec-Aging Inspection3/6/20193/6/20193/6/2019 1:15:42 PM DONE
Called TML and talked with Debbie about their mechanical aging permit. Schedule inspection with homeowner if work is finished.
MEC18-02529 Mec-Aging Inspection3/6/20193/6/20193/6/2019 1:10:25 PM DONE
Called CANFIELD HVAC and talked with Steve about their mechanical aging permit that needed corrections made on a failed final. Schedule inspection with home owner if corrections have been made.
MEC19-00794 Rough-in3/5/20193/6/20193/6/2019 1:05:01 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves
- floor boot needs sealed
- b vent in the attic needs 1 " clearances at roof
- 5lb flue pressure test fail
MEC19-00794 Pressure Test3/5/20193/6/20193/6/2019 1:03:34 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves
- 5lb flue pressure test fail gauge was at zero
- 20lb gas pressure test ok
- tagged meter location
MEC19-00933 Rough-in3/5/20193/6/20193/6/2019 1:02:19 PMAPASS
Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
- fireplace R/I ok
MEC19-00640 Rough-in3/5/20193/6/20193/6/2019 9:45:27 AMAPART
Bill Burch site contact. Phone #: ###-#### Inspection requested via web by RM Mechanical
- duct seal inspection ok on unit in gym
insulation cover ok this unit
- fresh airs for unit in gym and north side need to terminated side wall not through asphalt roof
MEC19-00934 Final3/5/20193/6/20193/6/2019 8:54:03 AMAPASS
SErgio Phone #: ###-####
- 2 exhaust fans and supply relocate ok