Inspections for the day of: Thursday, March 7, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00099 FIRE-Final Inspection3/6/20023/7/20023/7/2002 12:00:00 AMAPASS
fire life/safety finaled 3/7/2002 11:11:51 AM
BLD02-00422 FIRE-Final Inspection3/6/20023/7/20023/7/2002 12:00:00 AMAPART
Per Sam Rogers and Dave Miller it is OK for me to give a temp occ. The owner still needs to mount the fire extinguisher in the dining area at 48", provide annnual inspection tag for the fire riser and relocate or plug the two sprinkler pendants that are closer than 6' to one another. The kitchen hood had been tested Feb 27 3/7/2002 3:46:10 PM
FIR02-00041 INSP-Sprinkler Rough-in3/6/20023/7/20023/7/2002 12:00:00 AMAPASS
Fire sprinkler system rough-in OK. OK to cover 3/7/2002 10:21:09 AM
FIR01-00572 INSP-Supply line flush3/6/20023/7/20023/7/2002 12:00:00 AMAPASS
Underground flush OK 3/7/2002 9:20:26 AM
BLD01-02064 FIRE-Final Inspection3/6/20023/7/20023/7/2002 12:00:00 AMACANC
cancelled by contractor 3/7/2002 11:26:00 AM
FIR02-00040 INSP-Final Inspection3/7/20023/7/20023/7/2002 12:00:00 AMAPASS
Added by Inspector: 430 On 3/7/2002 10:20:07 AM Fire sprinkler system finaled
FIR01-00346 INSP-Final Inspection3/6/20023/7/20023/7/2002 12:00:00 AMPFAIL
All devices at beginning of test not working. Stopped test. Complete new inspection to be called in 3/7/2002 2:30:22 PM
FIR01-00590 INSP-Final Inspection3/6/20023/7/20023/7/2002 12:00:00 AMPFAIL
circuit wiring to duct detectors had been cut and needs repaired. Inspection stopped and not complete 3/7/2002 4:29:19 PM