Inspections for the day of: Friday, March 7, 2003.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00385 INSP-Supply line flush3/5/20033/7/20033/7/2003 12:00:00 AMAFAIL
The contractor is not getting enough flow for a flush due to 300' of hose. A minimum 880 gallons is required. Flush to be rescheduled 3/7/2003 11:21:48 AM
BLD02-01584 FIRE-Final Inspection3/6/20033/7/20033/7/2003 12:00:00 AMAFAIL
###-#### Need to provide manual shutdown for the ventilation system per UFC 8003.1.4.2 3/7/2003 10:56:20 AM
FIR02-00512 INSP-Final Inspection3/7/20033/7/20033/7/2003 12:00:00 AMPPART
phil; Phone #: ###-#### Tested most of the duct smoke detectors. They have been marked on the approved alarm plans. No other devices tested. Phil to provide print out of the alarm points for verification at central station 3/7/2003 4:07:04 PM
BLD02-02761 FIRE-Final Inspection3/7/20033/7/20033/7/2003 12:00:00 AMPFAIL
provide EQ bracing and hanger per code in the new tenant space, provide annual inspection for the fire sprinkler system, provide one additional sprinkler pendant near the front exit, provide approved fire alarm plans showing the two new duct smoke detectors supervised by the existing fire alarm system 3/7/2003 4:05:30 PM