FIR07-00625
| INSP-Final Inspection | 3/7/2008 | 3/7/2008 | 3/7/2008 4:05:56 PM | P | PASS |
|
|
Permit finaled
|
FIR07-00949
| INSP-Sprinkler Rough-in/Hydro | 3/7/2008 | 3/7/2008 | 3/7/2008 4:05:23 PM | P | PASS |
|
|
Sprinkler rough-in is passed. Will need a tenting inspection for the wet system prior to cover.
|
FIR08-00085
| INSP-Sprinkler Rough-in | 3/7/2008 | 3/7/2008 | 3/7/2008 3:35:45 PM | P | PASS |
|
|
The tenting inspection is passed. The sprinkler piping can be covered with the blow-in insulation.
|
BLD08-00260
| FIRE-Final Inspection | 3/6/2008 | 3/7/2008 | 3/7/2008 2:35:06 PM | P | PASS |
|
|
life safety passed.
|
FIR07-00972
| INSP-Final Inspection | 3/6/2008 | 3/7/2008 | 3/7/2008 2:34:08 PM | A | FAIL |
|
|
The west tenant work is passed. Stopped at the project twice but there is no access.
|
BLD08-00159
| FIRE-Final Inspection | 3/6/2008 | 3/7/2008 | 3/7/2008 11:29:27 AM | A | PASS |
|
|
Life safety passed.
|
BLD08-00396
| FIRE-Final Inspection | 3/6/2008 | 3/7/2008 | 3/7/2008 11:28:46 AM | A | FAIL |
|
|
Repair the emergency light in the west outdoor area. Provide verification that the south exit doors exit sign has battery backup. The nozzles for the hood suppression system need to be aligned with the appliances. The correct nozzles need to be supplied for the appliances. The appliances need to be positioned no closer than 6" to the inside edge of the hood. These are problems at both hoods.
|