Inspections for the day of: Monday, March 7, 2016.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02301 ELE-Aging Inspection3/7/20163/7/20163/14/2016 10:30:05 AM CANC
too busy
ELE16-00714 Temporary Service3/7/20163/7/20163/7/2016 3:04:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Richard Gratiot t/s u/g n ok
ELE16-00686 Temporary Service3/7/20163/7/20163/7/2016 2:57:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Robert Schroder t/s u/g n ok
ELE15-03117 Final3/7/20163/7/20163/7/2016 2:27:22 PMPFAIL
Please contact Greg Milburn at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce 440.22 protective device rating shall not exceed manufactures rating
ELE16-00264 Final3/7/20163/7/20163/7/2016 1:40:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack final ok
ELE16-00357 Final3/5/20163/7/20163/7/2016 1:09:02 PMPFAIL
The key is under the mat to the basement. IF you have any questions, please call Matt ###-####. Please call Dave ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 210.12 AFCI protection required for all bedrooms
ELE16-00713 Electrical Rough-In3/7/20163/7/20163/7/2016 12:34:14 PMPCANC
Please call half an hour in advance of inspection to insure access. Thanks Shaun 9###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman not ready at this time
ELE15-03729 Electrical Rough-In3/7/20163/7/20163/7/2016 12:32:07 PMPPASS
Rough-in rooms #106, 107, 112, 113, 205, 206, 207, 212, 213, 305, 306, 307, 312, 313. Phone #: ###-#### Inspection requested via web by Kerri Hamilton units 106,107,112,113,205,206,207,206,212,213,305,307,312,313,306 ok cover
ELE16-00404 Electrical Rough-In3/7/20163/7/20163/7/2016 12:08:03 PMPPASS
Phone #: ###-#### Inspection requested via web by Thaniel Bishop verified U/L ;istings and scope of work for solar array system
ELE16-00693 Final3/4/20163/7/20163/7/2016 11:47:56 AMPCANC
A/C disconnect Phone #: ###-#### Inspection requested via web by jamie berg cannot verify OCPD no access to panel
ELE16-00676 Final3/5/20163/7/20163/7/2016 11:17:06 AMACANC
Final inspect for Boise city pole lights
Contact: Tracy ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson power has not been swung yet
ELE15-03191 Final3/4/20163/7/20163/7/2016 11:02:26 AMAFAIL
would like call ahead; Rhonda Phone #: ###-#### 352.30 (a) PVC shall be supported with 36" of a cabinet 348.30 (a) FMC shall be supported 12" of a cabinet and not exceeding 4 1/2' 356.30 LFNC-B shall be supported with 12" of a box and not more the 6' 440.22 (c) protective device shall not exceed manufactures values (a/c)
ELE16-00715 Temporary Service3/7/20163/7/20163/7/2016 10:39:19 AMPPASS
Please call Jeff if you have any questions. Thanks Phone #: ###-#### Inspection requested via web by Brandon Blackham t/s u/g n ok
ELE16-00701 Electrical Rough-In3/4/20163/7/20163/7/2016 10:27:48 AMAPASS
bonding and u.g. cover of pool and spa Phone #: ###-#### Inspection requested via web by Kevin Koomler underground for pool@bonding of pool ok cover
ELE16-00694 Temporary Service3/4/20163/7/20163/7/2016 10:08:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE16-00695 Temporary Service3/4/20163/7/20163/7/2016 10:08:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE16-00708 Temporary Service3/4/20163/7/20163/7/2016 10:07:31 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE16-00292 Final3/5/20163/7/20163/7/2016 9:39:17 AMAPASS
Call for access Phone #: 2082214638 >> Inspection requested via mobile web by Matt corrections fixed final ok
ELE16-00690 Electrical Rough-In3/4/20163/7/20163/7/2016 9:32:51 AMAPASS
Need inspection to cover soffit in back barbecue area. Phone #: ###-#### Inspection requested via web by Alan Lusk bbq area soffit only ok cover
ELE16-00717 Conference3/7/20163/7/20163/7/2016 9:18:25 AMPCANC
Must be an AM inspection, we have already spoken with Eric and confirmed this was okay! Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON needed it on tuesday 3-8-16
ELE16-00710 Electrical Rough-In3/6/20163/7/20163/7/2016 9:17:00 AMAPASS
This rough In Is Ready For Inspection Call With Any Questions, The Home Owner Is There Thanks So Much! Dave Phone #: ###-#### Inspection requested via web by jason shifflett master bath ok cover