Inspections for the day of: Thursday, March 7, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00267 INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019 2:24:19 PMPPART
Partial rough to cover inspection for overhead fire sprinkler piping on level 3 complete, notated city approved drawings with areas approved for cover. Remaining sprinkler piping on level 2 inspected, all of level 2 approved for cover.

JUSTIN Phone #: ###-####
FIR18-00267 INSP-Sprinkler Rough-in/Hydro3/6/20193/7/20193/7/2019 2:22:20 PMPPART
Hydrostatic test for overhead fire sprinkler piping on level 3 witnessed, no pressure loss observed.

JUSTIN Phone #: ###-####
FIR18-00538 INSP-Final Inspection3/7/20193/7/20193/7/2019 10:59:58 AMPPASS
Final inspection for underground supply completed on 01MAR2019
BLD19-00554 FIRE-Final Inspection3/6/20193/7/20193/7/2019 10:44:44 AMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher will be mounted in discussed location. Final life fire safety inspection for area of work complete.

Jay Phone #: ###-####
FIR18-00828 INSP-Sprinkler Rough-in3/6/20193/7/20193/7/2019 10:00:18 AMAPASS
All tenting in place at time of inspection, level 3 approved for cover.

Gabe Garduno is the contact for this RTC inspection for building E. He is requesting the inspection for the 3rd floor. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00544 INSP-Sprinkler Rough-in/Hydro3/6/20193/7/20193/7/2019 9:59:43 AMADONE
Hydrostatic test witnessed for undergorund supply, no pressure loss observed.

Gabe Garduno is the contact for this underground hydro inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD19-00675 FIRE-Final Inspection3/6/20193/7/20193/7/2019 12:00:00 AMPCANC
Lesley Phone #: ###-####
BLD18-01753 FIRE-Final Inspection3/6/20193/7/20193/6/2019 3:23:20 PMAPART
Final inspection for life fire safety inspection complete, TCO authorized for 30 days per conversation with Ron Johnson with the contingent of the fire alarm and fire sprinkler as-builts being submitted and approved. Once FIR permit as-builts are submitted, approved and the inspection status is finaled then life fire safety can be scheduled and completed.

temp Phone #: ###-####