Inspections for the day of: Monday, March 8, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00151 INSP-Conference3/8/20043/8/20043/8/2004 12:00:00 AMADONE
I stopped at the job site and posted a stop work order against the fire alarm system. The fire alarm panel and conduit have been installed by Idaho Electric. The installers name is Neil Lake. I spoke to Brad, who is the owner of Idaho Electric, about not installing without approved plans. I also spoke to Patrick with system services who actually submitted the plans.
BLD02-02873 FIRE-Final Inspection3/8/20043/8/20043/8/2004 12:00:00 AMPPASS
fire life safety finaled 3/8/2004 3:22:08 PM
FIR04-00086 INSP-Alarm Testing3/5/20043/8/20043/8/2004 12:00:00 AMPPASS
fire alarm finaled 3/8/2004 4:10:22 PM
FIR03-00794 INSP-Final Inspection3/5/20043/8/20043/8/2004 12:00:00 AMPPASS
fire sprinklers finaled 3/8/2004 4:10:31 PM
FIR03-00295 INSP-Final Inspection3/8/20043/8/20043/8/2004 12:00:00 AMPPASS
Fire sprinklers finaled 3/8/2004 9:54:18 AM
MIS04-00074 FIR-Final3/8/20043/8/20043/8/2004 12:00:00 AMPFAIL
Provide "Door to remain unlocked during business hours" sticker and provide approved door hardware on the second exterior exit door. 3/8/2004 11:32:10 AM
FIR04-00104 INSP-Alarm Testing3/5/20043/8/20043/5/2004 8:08:00 AMPCANC
Scheduled by a contractor via Hello! on 3/5/2004 at 7:55:56 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Mar 5 2004 8:08AM.