Inspections for the day of: Tuesday, March 8, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00747 FIR-Aging Inspection3/8/20053/8/20053/8/2005 12:00:00 AM NR
wip 3/9/2005 2:54:59 PM
FIR04-00536 INSP-Supply line flush3/3/20053/8/20053/8/2005 12:00:00 AMAPASS
Underground supply line flush passed 3/8/2005 9:54:16 AM
FIR05-00086 INSP-Sprinkler Rough-in/Hydro3/7/20053/8/20053/8/2005 12:00:00 AMAPASS
sprinkler piping is ok to cover 3/8/2005 9:19:15 AM
FIR03-00796 INSP-Final Inspection3/7/20053/8/20053/8/2005 12:00:00 AMAFAIL
Provide correct orfice in the inspectors test and test the flow switch. Relocate the smoke detector to the deck and test. Provide nfpa 72 forms 3/8/2005 10:47:05 AM
FIR05-00008 INSP-Final Inspection3/7/20053/8/20053/8/2005 12:00:00 AMAFAIL
Approved fire sprinkler plans do not match installation. Pendants have been deleted in the door pockets, upright heads added under ductwork and in void spaces. 90's have been added in the 3" supply. I could not get access to verify tie in to the existing 3" feed. Auxillary drain has been added above the ceiling at the end of the new 3" main. Resubmit plans or verify if as builts will be acceptable for the changes. 3/8/2005 4:40:06 PM
FIR05-00095 INSP-Sprinkler Rough-in3/7/20053/8/20053/8/2005 12:00:00 AMACANC
check insulation,,, call 415 1st
FIR05-00084 INSP-Conference3/7/20053/8/20053/8/2005 12:00:00 AMPDONE
nick///for box lacations; Phone #: ###-#### Internet Inspection Request from: Barbara Moore

Verified box locations, a H/S on northeast wall shifted, it could be a problem if the cubicle walls are greater than 6'. Nick stated that they are having to shift remote test switches for existing duct detectors. I told him to keep track of all FA changes and to resubmit a "plan modification" about a week prior to the final inspection.
BLD04-00847 FIRE-Final Inspection3/7/20053/8/20053/8/2005 12:00:00 AMPPART
vince; Phone #: ###-#### Items on the correction notice have been corrected. Need to help with location for exit signs in basement to first floor. 3/8/2005 4:43:22 PM
FIR05-00081 INSP-Final Inspection3/7/20053/8/20053/8/2005 12:00:00 AMPFAIL
Provide correct zone descriptions, provide map at facp, change new zone to "Anti-freeze tamper", verify signals. 3/8/2005 4:46:13 PM
FIR05-00100 INSP-Alarm Testing3/8/20053/8/20053/8/2005 12:00:00 AMPPART
Started inspection on the first floor. See approved plans for devices tested and locations of deficiencies. 3/8/2005 4:42:04 PM
BLD04-02809 FIRE-Final Inspection3/8/20053/8/20053/8/2005 12:00:00 AMPFAIL
rod; Phone #: ###-#### Life safety will be ok to final when alarms and fire sprinkler permits are finaled. 3/8/2005 4:41:02 PM
FIR04-00368 INSP-Final Inspection3/8/20053/8/20053/8/2005 12:00:00 AMPPASS
fire sprinklers finaled 3/8/2005 2:51:19 PM
BLD05-00082 FIRE-Conference3/8/20053/8/20053/8/2005 12:00:00 AMPCANC
marty; Phone #: ###-#### Note: please call 1/2 hr prior to inspection Internet Inspection Request from: Cathy Chiles