ELE05-01561
| ELE-Aging Inspection | 3/8/2006 | 3/8/2006 | 3/14/2006 7:33:00 AM | | PART |
|
|
wsuc
|
ELE05-00344
| Final | 3/8/2006 | 3/8/2006 | 3/8/2006 1:05:12 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/8/2006 at 11:12:38 AM. corr. posted called reinspection fee due, 250.32(B)(1) shall isolate grds and neutrals at p/s, 250.8 no SMS allowed, 250.50,52(A)(1)or104(A)(1) grd or bond water system, 312.5 needs conn for GEC, 110.3(B) use manufactures breakers only,408.4 circuit directory, 250.130 open grd gfci recept in restrm contractor has 5 working days too correct, complete, and call for reinspection
|
ELE06-00796
| Conference | 3/8/2006 | 3/8/2006 | 3/8/2006 12:16:44 PM | P | DONE |
|
|
###-#### - greg
|
ELE05-03564
| Final | 3/7/2006 | 3/8/2006 | 3/8/2006 10:30:38 AM | A | PASS |
|
|
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
|
ELE06-00116
| Electrical Rough-In | 3/7/2006 | 3/8/2006 | 3/8/2006 9:43:58 AM | A | PART |
|
|
Mike -- underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong u/g for office area only needs documuntation for repair garage and spray booth areas
|
ELE06-00785
| Temporary Service | 3/7/2006 | 3/8/2006 | 3/8/2006 9:11:37 AM | A | FAIL |
|
|
Brian; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called needs clearence over alley, needs conn for GEC, shall not ID #6 or smaller needs white
|
ELE06-00786
| Electrical Rough-In | 3/7/2006 | 3/8/2006 | 3/8/2006 8:52:33 AM | A | PASS |
|
|
Keith or Diane -- call 1st before insp; connecting power from pedestal to mobile home; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong trench and u/g ok
|
ELE05-03537
| ELE-Aging Inspection | 3/8/2006 | 3/8/2006 | 3/8/2006 8:14:28 AM | | PASS |
|
|
|
ELE05-04385
| ELE-Aging Inspection | 3/8/2006 | 3/8/2006 | 3/8/2006 7:47:20 AM | | PASS |
|
|
|
ELE05-04385
| DOC - Permit Finaled | 3/8/2006 | 3/8/2006 | 3/8/2006 12:00:00 AM | A | PASS |
|
|
|
ELE05-03537
| DOC - Permit Finaled | 3/8/2006 | 3/8/2006 | 3/8/2006 12:00:00 AM | A | PASS |
|
|
added sign to existing sign
|
ELE06-00786
| DOC - Permit Finaled | 3/8/2006 | 3/8/2006 | 3/8/2006 12:00:00 AM | A | PASS |
|
|
Keith or Diane -- call 1st before insp; connecting power from pedestal to mobile home; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
|