Inspections for the day of: Wednesday, March 8, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01561 ELE-Aging Inspection3/8/20063/8/20063/14/2006 7:33:00 AM PART
wsuc
ELE05-00344 Final3/8/20063/8/20063/8/2006 1:05:12 PMPFAIL
Scheduled by a contractor via Hello! on 3/8/2006 at 11:12:38 AM. corr. posted called reinspection fee due, 250.32(B)(1) shall isolate grds and neutrals at p/s, 250.8 no SMS allowed, 250.50,52(A)(1)or104(A)(1) grd or bond water system, 312.5 needs conn for GEC, 110.3(B) use manufactures breakers only,408.4 circuit directory, 250.130 open grd gfci recept in restrm contractor has 5 working days too correct, complete, and call for reinspection
ELE06-00796 Conference3/8/20063/8/20063/8/2006 12:16:44 PMPDONE
###-#### - greg
ELE05-03564 Final3/7/20063/8/20063/8/2006 10:30:38 AMAPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
ELE06-00116 Electrical Rough-In3/7/20063/8/20063/8/2006 9:43:58 AMAPART
Mike -- underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong u/g for office area only needs documuntation for repair garage and spray booth areas
ELE06-00785 Temporary Service3/7/20063/8/20063/8/2006 9:11:37 AMAFAIL
Brian; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
called needs clearence over alley, needs conn for GEC, shall not ID #6 or smaller needs white
ELE06-00786 Electrical Rough-In3/7/20063/8/20063/8/2006 8:52:33 AMAPASS
Keith or Diane -- call 1st before insp; connecting power from pedestal to mobile home; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong trench and u/g ok
ELE05-03537 ELE-Aging Inspection3/8/20063/8/20063/8/2006 8:14:28 AM PASS
ELE05-04385 ELE-Aging Inspection3/8/20063/8/20063/8/2006 7:47:20 AM PASS
ELE05-04385 DOC - Permit Finaled3/8/20063/8/20063/8/2006 12:00:00 AMAPASS
ELE05-03537 DOC - Permit Finaled3/8/20063/8/20063/8/2006 12:00:00 AMAPASS
added sign to existing sign
ELE06-00786 DOC - Permit Finaled3/8/20063/8/20063/8/2006 12:00:00 AMAPASS
Keith or Diane -- call 1st before insp; connecting power from pedestal to mobile home; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong