Inspections for the day of: Wednesday, March 8, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04387 ELE-Aging Inspection3/8/20063/8/20063/9/2006 9:41:23 AM DONE
suc
ELE05-04422 ELE-Aging Inspection3/8/20063/8/20063/9/2006 8:25:35 AM DONE
suc
ELE05-04388 ELE-Aging Inspection3/8/20063/8/20063/9/2006 8:23:02 AM DONE
see final
ELE06-00781 Final3/8/20063/8/20063/8/2006 5:04:48 PMPPASS
Mrs. Sanders ###-####-- (Kevin - Retro Electric ###-####); ok per Bob Reichert 3-8-06 eus called contr, told him he shall update grounding for service. he added 1 additional ground rod. ok to final
ELE05-04465 Final3/8/20063/8/20063/8/2006 3:41:55 PMPPASS
Alan; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok to final
ELE06-00769 Final3/7/20063/8/20063/8/2006 3:03:23 PMAPASS
READY FOR FINAL, PLEASE CONTACT RON, THANK YOU; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to final, talked to contr about service that shall be moved. No permit posted, front of panel is on metel roof. Owner and contr indicate they will take care of.
ELE05-00855 Electrical Rough-In3/8/20063/8/20063/8/2006 2:47:57 PMPPART
CONTACT: LYLE DEAN - TEMPORARY OCCUPANCY INSPECTION PLEASE.; Phone #: ###-#### Internet Inspection Request from: Deb McCoy signed t/o card for first 3 floors of parking garage only
ELE06-00394 Final3/8/20063/8/20063/8/2006 12:44:58 PMPFAIL
Chuck; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr notice, 408.4 circuit directory shall be complete, clear, and provide detail for purpose, 406.4 receptacles shall be securely mounted and fastened in place, 334.30 nm cable shall be secured within 12" of box(out of panel), 406.8(B) outside gfci receptacle shall have cover that is weatherproof whether or not attachment plug cap is inserted.
ELE06-00788 Rough-In Permanent Service3/7/20063/8/20063/8/2006 10:28:23 AMAPASS
Paul; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ric ok, p/s u/g n ok
ELE06-00695 Rough-In Permanent Service3/6/20063/8/20063/8/2006 10:04:00 AMAPASS
Steve; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ric ok, p/s u/g n ok
ELE06-00794 Final3/7/20063/8/20063/8/2006 9:28:32 AMAPASS
READY FOR FINAL, PELASE CONTACT RON, THANK YOU; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to final
ELE06-00719 Rough-In Permanent Service3/7/20063/8/20063/8/2006 8:47:17 AMAPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ric ok, p/s u/g n ok