ELE05-04387
| ELE-Aging Inspection | 3/8/2006 | 3/8/2006 | 3/9/2006 9:41:23 AM | | DONE |
|
|
suc
|
ELE05-04422
| ELE-Aging Inspection | 3/8/2006 | 3/8/2006 | 3/9/2006 8:25:35 AM | | DONE |
|
|
suc
|
ELE05-04388
| ELE-Aging Inspection | 3/8/2006 | 3/8/2006 | 3/9/2006 8:23:02 AM | | DONE |
|
|
see final
|
ELE06-00781
| Final | 3/8/2006 | 3/8/2006 | 3/8/2006 5:04:48 PM | P | PASS |
|
|
Mrs. Sanders ###-####-- (Kevin - Retro Electric ###-####); ok per Bob Reichert 3-8-06 eus called contr, told him he shall update grounding for service. he added 1 additional ground rod. ok to final
|
ELE05-04465
| Final | 3/8/2006 | 3/8/2006 | 3/8/2006 3:41:55 PM | P | PASS |
|
|
Alan; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok to final
|
ELE06-00769
| Final | 3/7/2006 | 3/8/2006 | 3/8/2006 3:03:23 PM | A | PASS |
|
|
READY FOR FINAL, PLEASE CONTACT RON, THANK YOU; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to final, talked to contr about service that shall be moved. No permit posted, front of panel is on metel roof. Owner and contr indicate they will take care of.
|
ELE05-00855
| Electrical Rough-In | 3/8/2006 | 3/8/2006 | 3/8/2006 2:47:57 PM | P | PART |
|
|
CONTACT: LYLE DEAN - TEMPORARY OCCUPANCY INSPECTION PLEASE.; Phone #: ###-#### Internet Inspection Request from: Deb McCoy signed t/o card for first 3 floors of parking garage only
|
ELE06-00394
| Final | 3/8/2006 | 3/8/2006 | 3/8/2006 12:44:58 PM | P | FAIL |
|
|
Chuck; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr notice, 408.4 circuit directory shall be complete, clear, and provide detail for purpose, 406.4 receptacles shall be securely mounted and fastened in place, 334.30 nm cable shall be secured within 12" of box(out of panel), 406.8(B) outside gfci receptacle shall have cover that is weatherproof whether or not attachment plug cap is inserted.
|
ELE06-00788
| Rough-In Permanent Service | 3/7/2006 | 3/8/2006 | 3/8/2006 10:28:23 AM | A | PASS |
|
|
Paul; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ric ok, p/s u/g n ok
|
ELE06-00695
| Rough-In Permanent Service | 3/6/2006 | 3/8/2006 | 3/8/2006 10:04:00 AM | A | PASS |
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ric ok, p/s u/g n ok
|
ELE06-00794
| Final | 3/7/2006 | 3/8/2006 | 3/8/2006 9:28:32 AM | A | PASS |
|
|
READY FOR FINAL, PELASE CONTACT RON, THANK YOU; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to final
|
ELE06-00719
| Rough-In Permanent Service | 3/7/2006 | 3/8/2006 | 3/8/2006 8:47:17 AM | A | PASS |
|
|
darrell; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ric ok, p/s u/g n ok
|