ELE07-00174
| Final | 3/7/2007 | 3/8/2007 | 3/8/2007 3:08:30 PM | P | FAIL |
|
|
Contact: Bob Phone #: ###-#### corr see notes for permit ele07-00167
|
ELE07-00175
| Final | 3/7/2007 | 3/8/2007 | 3/8/2007 3:07:45 PM | P | FAIL |
|
|
Contact: Bob Phone #: ###-#### corr see notes for permit ele07-00167
|
ELE07-00176
| Final | 3/7/2007 | 3/8/2007 | 3/8/2007 3:06:52 PM | P | FAIL |
|
|
Contact: Bob Phone #: ###-#### corr see notes for permit # ele07-00167
|
ELE07-00167
| Final | 3/7/2007 | 3/8/2007 | 3/8/2007 3:05:58 PM | P | FAIL |
|
|
Contact is Bob Phone #: ###-#### corr called 410.8 clearence upstairs closets, 250.118(5)&148 shall use grd screws or clip too grd box extension, and blank covers at funaces, 225.31&36 shall provide disconnects at garages, 408.4 panel directories shall be specific for purpose and use
|
ELE07-00776
| Electrical Rough-In | 3/8/2007 | 3/8/2007 | 3/8/2007 1:25:53 PM | P | FAIL |
|
|
corr called shall have approved plans on site that match kitchen layout, 210.52(C)(1) shall install required outlet above countertop for spacing right of refer by window
|
ELE07-00776
| Electrical Rough-In | 3/8/2007 | 3/8/2007 | 3/8/2007 1:22:45 PM | P | CANC |
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Victoria see added r/i
|
ELE07-00776
| Permanent Service | 3/8/2007 | 3/8/2007 | 3/8/2007 1:20:48 PM | P | PASS |
|
|
chad; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s u/g new ok
|
ELE07-00780
| Electrical Rough-In | 3/8/2007 | 3/8/2007 | 3/8/2007 12:19:01 PM | P | PART |
|
|
eric; Phone #: ###-#### Internet Inspection Request from: Victoria Beall electrode ok for concrete cover
|
ELE06-03518
| Final | 3/5/2007 | 3/8/2007 | 3/8/2007 9:05:56 AM | A | PASS |
|
|
mitch; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok
|
ELE07-00447
| Electrical Rough-In | 3/7/2007 | 3/8/2007 | 3/8/2007 8:41:17 AM | A | PART |
|
|
glen - dining room phase; Phone #: ###-#### Internet Inspection Request from: Victoria Beall din. walls ceilings
|
ELE06-02800
| Final | 3/7/2007 | 3/8/2007 | 3/8/2007 8:23:20 AM | A | PASS |
|
|
reinspection Phone #: ###-#### x0000 ok card signed
|
ELE06-03280
| Electrical Rough-In | 3/7/2007 | 3/8/2007 | 3/8/2007 7:45:49 AM | A | PART |
|
|
Please inspect underground of MDP room (near D-wing). Thankyou. Phone #: ###-#### u/g ok
|