Inspections for the day of: Thursday, March 8, 2007.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00584 FIR-Aging Inspection3/8/20073/8/20073/12/2007 2:33:58 PM DONE
Phone call to contractor to determine status, work in progress.
BLD05-00775 FIRE-Final Inspection3/8/20073/8/20073/8/2007 3:36:08 PMPPASS
Final fire life safety walk through passed inspection, some issues corrected while on site, previous c/n items are complete.
FIR07-00020 INSP-Final Inspection3/8/20073/8/20073/8/2007 3:33:35 PMPPASS
Final inspection passed, permit finaled.
FIR07-00104 INSP-Final Inspection3/8/20073/8/20073/8/2007 3:32:40 PMPPASS
Fire alarm passed, permit finaled.
FIR06-00667 INSP-Final Inspection3/8/20073/8/20073/8/2007 2:08:28 PMPPASS
Final alarm inspection passed, permit finaled.
FIR07-00015 INSP-Alarm Testing3/7/20073/8/20073/8/2007 1:57:10 PMAPART
Fire alarm testing for the area north of the hallway as red lined on approved plans is satisfactory.
FIR07-00104 INSP-Alarm Testing3/7/20073/8/20073/8/2007 12:44:01 PMAPASS
Fire alarm testing completed satisfactory.
FIR06-00671 INSP-Final Inspection3/7/20073/8/20073/8/2007 12:36:17 PMAFAIL
Ordinary temp SW heads in the skylights on the second floor are not permitted, need to provide a "911" sign at the outside bell, contractor to provide a pitot guage and playpipes to enable forward flow testing of the BFP as indicated in plan attatched fire code review notes.