Inspections for the day of: Tuesday, March 8, 2011.
Number of inspections: 1
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTim Frost
TitleFIRE PLANS EXAMINER
Phone #208-608-7110
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00569 INSP-Sprinkler Rough-in/Hydro3/8/20113/8/20113/8/2011 12:00:00 AMPDONE
Hydro passed.
Rough in passed except for adding one brace to the main where a new offset was added. The hydraulics had enough cushion that the offset did not adversely affect the hydraulic calculation. One drop plug in restroom awaiting ceiling.