Inspections for the day of: Wednesday, March 8, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00787 INSP-Sprinkler Rough-in3/8/20173/8/20173/8/2017 3:26:04 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR16-00790 INSP-Sprinkler Rough-in3/8/20173/8/20173/8/2017 3:25:41 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR16-00786 INSP-Sprinkler Rough-in3/8/20173/8/20173/8/2017 3:24:48 PMPPASS
Rough to cover inspection for underground supply complete, approved for cover.
FIR16-00511 INSP-Sprinkler Rough-in/Hydro3/7/20173/8/20173/8/2017 2:29:03 PMPPART
Hydro for overhead fire sprinkler piping on levels 1, 2 and 4 complete, level 3 lost pressure, will need to have hydro test completed again for level 3 after repair is made. Rough to cover inspection /tenting inspection complete, all can be covered with exception to the appartment with the 2 inch CPVC suppling the riser from the standpipe/FDC, no hangers were on the 2 inch at time of inspection.
FIR16-00512 INSP-Supply line flush3/7/20173/8/20173/8/2017 12:51:00 PMPPART
Inspection request is for underground rough/hydro, not supply line flush. Underground rough to cover inspection complete, underground hydro complete.
FIR16-00511 INSP-Supply line flush3/7/20173/8/20173/8/2017 12:50:29 PMPPART
Inspection request is for underground rough/hydro, not supply line flush. Underground rough to cover inspection complete, underground hydro complete.