Inspections for the day of: Thursday, March 8, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00872 Final3/7/20183/8/20183/8/2018 1:58:13 PMPPASS
Neil added a dedicated circuit for ATM machine Phone #: ###-#### Inspection requested via web by Matthew White Final ok
ELE18-00872 Electrical Rough-In3/8/20183/8/20183/8/2018 1:57:39 PMPPASS
Neil added a dedicated circuit for ATM machine Phone #: ###-#### Inspection requested via web by Matthew White
30' of MC used to feed 277 volt sign on top of ATM machine. Rough in ok
ELE18-00352 Permanent Service3/7/20183/8/20183/8/2018 1:40:17 PMPPASS
Please inspect the meter pack on the left. Thanks Phone #: ###-#### Inspection requested via web by Ryan Wilson
Available fault current posted 9,987 amp on 10K reated mains.
Left service only p/s u/g n ok
ELE18-00727 Electrical Rough-In3/8/20183/8/20183/8/2018 1:27:47 PMPPASS
Underground inspection Phone #: ###-#### Inspection requested via web by Tom Jenkins
Feeder underground conduits rough in ok cover
ELE18-00746 Rough-In Permanent Service3/8/20183/8/20183/8/2018 11:39:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE17-03983 Final3/7/20183/8/20183/8/2018 10:56:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Duplicate permit for temp pole. No longer needed. Final ok to clear off books
ELE17-04048 Final3/8/20183/8/20183/8/2018 10:55:26 AMPFAIL
408.4- Circuit directory shall be complete.
422.30- Disconnecting means shall be provided for range hood. lockout acceptable as per 110.25.
ELE18-00861 Rough-In Permanent Service3/6/20183/8/20183/8/2018 10:00:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE18-00876 Rough-In Permanent Service3/7/20183/8/20183/8/2018 9:23:17 AMAFAIL
Phone #: ###-#### Inspection requested via web by Heath Thomas
110.26- Work space shall be povided for meter base. 30" wide and 36" deep.
ELE18-00876 Electrical Rough-In3/8/20183/8/20183/8/2018 9:22:58 AMPPASS
Phone #: ###-#### Inspection requested via web by Heath Thomas
Rough in ok cover