ELE19-00826
| Electrical Rough-In | 3/8/2019 | 3/8/2019 | 3/8/2019 3:14:40 PM | P | CANC |
|
|
Brandon-but call homeowner when on way Rick ###-#### Phone #: ###-#### Owner asked to reschedule, he is busy at work
|
ELE19-00809
| Final | 3/8/2019 | 3/8/2019 | 3/8/2019 2:46:03 PM | P | NH |
|
|
gas furnace wiring ready for inspection. Tenant should be there this afternoon Phone #: ###-#### Inspection requested via web by Kelly Felin Door locked, note stated all agents at jail. Recall when accessible
|
ELE18-03892
| Final | 3/7/2019 | 3/8/2019 | 3/8/2019 2:28:44 PM | P | FAIL |
|
|
Etta Phone #: ###-#### 110.3- Open ground and up receptacle not working. Mechanical room and pantry show open grounds. 250.140- Range and dryers shall be 4 wire receptacles. 210.70- Exterior lights shall operate at all exterior entrances. finish patio ceiling. 314.16- Disposal box shall have 16 cubic inch minimum for conductors installed. 314.29- Boxes shall be fully accessible under cooktop. 334.12- NM cable shall be protected from damage under sink and shall not be installed in damp locations. Patio. 348.30- Strap furnace flex with in 12" of a box and rest not to exceed 3'. 406.6- Receptacles and switches shall have proper covers. few missing. 406.9- Receptacles installed outdoors shall be weather resistant type. Near AC. 422.31- Appliances shalll have a disconnecting means. 110.25 lockouts acceptable. Oven, dishwasher, range hood. 440.11- Furnace shall have a manual disconnecting means.
|
ELE19-00750
| Final | 3/8/2019 | 3/8/2019 | 3/8/2019 11:52:46 AM | P | PASS |
|
|
Clerical issue on issued state of permit. Final ok
|
ELE19-00750
| Final | 3/7/2019 | 3/8/2019 | 3/8/2019 11:26:47 AM | A | FAIL |
|
|
Job is ready to go homeowner will give access have a great weekend Phone #: ###-#### Inspection requested via web by TRENT Swaim Building permit has not been issued. Unable to inspect until BLD is issued. Recall when ready. Called contact.
|
ELE19-00678
| Rough-In Permanent Service | 3/7/2019 | 3/8/2019 | 3/8/2019 10:58:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by shane miller Service only p/s o/h n ok
|
ELE19-00198
| Final | 3/7/2019 | 3/8/2019 | 3/8/2019 10:34:34 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 210.52(C)- Pantry counter top area shall have receptacle outlets installed so that no point measured along wall line horizontally is more than 24" from a receptacle outlet.
|
ELE19-00631
| Electrical Rough-In | 3/7/2019 | 3/8/2019 | 3/8/2019 9:13:57 AM | A | PASS |
|
|
Please call Bob at ###-#### first thing in the morning. Thanks Phone #: ###-#### Inspection requested via web by Kerri Hamilton North east corner under slab rough in ok cover
|
ELE19-00826
| Final | 3/8/2019 | 3/8/2019 | 3/8/2019 12:00:00 AM | P | DONE |
|
|
call owner at ###-#### for access Phone #: ###-#### >> Inspection requested via web by Brandon Winters
|