FIR04-00666
| INSP-Sprinkler Rough-in/Hydro | 3/3/2005 | 3/9/2005 | 3/9/2005 9:34:24 AM | P | CANC |
|
|
Contact: Brian -- AG and UG 200 lb hydro test. Would like around 11:30; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
FIR04-00745
| FIR-Aging Inspection | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | | NR |
|
|
Per Chris this project is on hold due to design concerns on the fire alarm. Kathy Horton with Idaho Power is the contact. 3/9/2005 10:02:12 AM
|
FIR04-00708
| FIR-Aging Inspection | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | | NR |
|
|
work in progress 3/9/2005 9:42:28 AM
|
FIR05-00100
| INSP-Alarm Testing | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | A | PART |
|
|
See approved plans and electricians notes for deficiencies for first floor and the east half of the second floor 3/9/2005 11:37:37 AM
|
BLD02-00966
| FIRE-Final Inspection | 3/8/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled. Per Dave Miller the new fire hydrant located in the developement next door is adequate for this project 3/9/2005 10:00:40 AM
|
MIS04-00319
| FIR-Final | 3/8/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given until the fire extinguisher has been relocated to a normal path of travel. 3/9/2005 9:31:09 AM
|
FIR04-00792
| INSP-Alarm Testing | 3/8/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/8/2005 at 4:39:24 PM. Contact: ###-####.
|
FIR04-00787
| INSP-Alarm Testing | 3/8/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | A | PASS |
|
|
fire alarm finaled 3/11/2005 9:53:03 AM
|
FIR04-00765
| INSP-Alarm Testing | 3/8/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | A | CANC |
|
|
To be rescheduled for next tuesday 3/11/2005 9:54:08 AM
|
BLD04-01073
| FIRE-Final Inspection | 3/8/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | FAIL |
|
|
Provide exit signs and emergency light at the north east exit. Provide battery backup in the two exit signs out the main exit 3/9/2005 4:04:13 PM
|
FIR04-00619
| INSP-Supply line flush | 3/8/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | PASS |
|
|
Underground supply line flush passed 3/9/2005 4:04:56 PM
|
BLD04-02124
| FIRE-Final Inspection | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | FAIL |
|
|
relocate duct detectors as discussed 3/9/2005 2:46:55 PM
|
FIR05-00050
| INSP-Final Inspection | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | PASS |
|
|
Hood suppression system operated correctly. The only appliance under the hood is a small oven 3/10/2005 8:54:59 AM
|
FIR04-00694
| INSP-Final Inspection | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | PART |
|
|
Phase four area is ok to cover will be finaled at building final 3/9/2005 2:00:19 PM
|
MIS05-00030
| FIR-Final | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | PART |
|
|
A temporary occupancy was given until all exit signs and emergency lights in the egress corridors and stairwells are repaired and tested. Remove the thumbturn locks off of both exit doors from tenant space. 3/9/2005 11:26:58 AM
|
BLD04-01896
| FIRE-Final Inspection | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | FAIL |
|
|
See correction notice for items remaining. They include fire alarm and fire sprinkler permits for work to be done. 3/9/2005 12:39:26 PM
|
BLD04-02877
| FIRE-Final Inspection | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | FAIL |
|
|
See fire dept review notes for my comments on items needing verified. 3/9/2005 12:39:53 PM
|
BLD05-00133
| FIRE-Conference | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | DONE |
|
|
Went over life safety items with contractor 3/10/2005 8:53:57 AM
|
FIR04-00593
| INSP-Sprinkler Rough-in/Hydro | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | PASS |
|
|
kerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
2" main running east to west, top floor, south bedroom, 2 X 11/2" X 1, shop thread tee leaked, will be repaired. East attic upright, in the top floor north bedroom is obstructed and needs corrected. Other grooved coupling (3 or 4) leaking appeared to stop after field adjustments. JWA
|
BLD03-02084
| FIRE-Final Inspection | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | FAIL |
|
|
Need to final the fire alarm permit. Add exit signs on east end of all floors as discussed and provide two additional fire extinguishers, one near the pool area and one near front desk 3/10/2005 3:49:09 PM
|
FIR04-00666
| INSP-Sprinkler Rough-in/Hydro | 3/9/2005 | 3/9/2005 | 3/9/2005 12:00:00 AM | P | CANC |
|
|
not ready until tomorrow 3/9/2005 12:56:19 PM
|