Inspections for the day of: Wednesday, March 9, 2005.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00666 INSP-Sprinkler Rough-in/Hydro3/3/20053/9/20053/9/2005 9:34:24 AMPCANC
Contact: Brian -- AG and UG 200 lb hydro test. Would like around 11:30; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
FIR04-00745 FIR-Aging Inspection3/9/20053/9/20053/9/2005 12:00:00 AM NR
Per Chris this project is on hold due to design concerns on the fire alarm. Kathy Horton with Idaho Power is the contact. 3/9/2005 10:02:12 AM
FIR04-00708 FIR-Aging Inspection3/9/20053/9/20053/9/2005 12:00:00 AM NR
work in progress 3/9/2005 9:42:28 AM
FIR05-00100 INSP-Alarm Testing3/9/20053/9/20053/9/2005 12:00:00 AMAPART
See approved plans and electricians notes for deficiencies for first floor and the east half of the second floor 3/9/2005 11:37:37 AM
BLD02-00966 FIRE-Final Inspection3/8/20053/9/20053/9/2005 12:00:00 AMAPASS
Fire life safety finaled. Per Dave Miller the new fire hydrant located in the developement next door is adequate for this project 3/9/2005 10:00:40 AM
MIS04-00319 FIR-Final3/8/20053/9/20053/9/2005 12:00:00 AMAPART
A temporary occupancy was given until the fire extinguisher has been relocated to a normal path of travel. 3/9/2005 9:31:09 AM
FIR04-00792 INSP-Alarm Testing3/8/20053/9/20053/9/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 3/8/2005 at 4:39:24 PM. Contact: ###-####.
FIR04-00787 INSP-Alarm Testing3/8/20053/9/20053/9/2005 12:00:00 AMAPASS
fire alarm finaled 3/11/2005 9:53:03 AM
FIR04-00765 INSP-Alarm Testing3/8/20053/9/20053/9/2005 12:00:00 AMACANC
To be rescheduled for next tuesday 3/11/2005 9:54:08 AM
BLD04-01073 FIRE-Final Inspection3/8/20053/9/20053/9/2005 12:00:00 AMPFAIL
Provide exit signs and emergency light at the north east exit. Provide battery backup in the two exit signs out the main exit 3/9/2005 4:04:13 PM
FIR04-00619 INSP-Supply line flush3/8/20053/9/20053/9/2005 12:00:00 AMPPASS
Underground supply line flush passed 3/9/2005 4:04:56 PM
BLD04-02124 FIRE-Final Inspection3/9/20053/9/20053/9/2005 12:00:00 AMPFAIL
relocate duct detectors as discussed 3/9/2005 2:46:55 PM
FIR05-00050 INSP-Final Inspection3/9/20053/9/20053/9/2005 12:00:00 AMPPASS
Hood suppression system operated correctly. The only appliance under the hood is a small oven 3/10/2005 8:54:59 AM
FIR04-00694 INSP-Final Inspection3/9/20053/9/20053/9/2005 12:00:00 AMPPART
Phase four area is ok to cover will be finaled at building final 3/9/2005 2:00:19 PM
MIS05-00030 FIR-Final3/9/20053/9/20053/9/2005 12:00:00 AMPPART
A temporary occupancy was given until all exit signs and emergency lights in the egress corridors and stairwells are repaired and tested. Remove the thumbturn locks off of both exit doors from tenant space. 3/9/2005 11:26:58 AM
BLD04-01896 FIRE-Final Inspection3/9/20053/9/20053/9/2005 12:00:00 AMPFAIL
See correction notice for items remaining. They include fire alarm and fire sprinkler permits for work to be done. 3/9/2005 12:39:26 PM
BLD04-02877 FIRE-Final Inspection3/9/20053/9/20053/9/2005 12:00:00 AMPFAIL
See fire dept review notes for my comments on items needing verified. 3/9/2005 12:39:53 PM
BLD05-00133 FIRE-Conference3/9/20053/9/20053/9/2005 12:00:00 AMPDONE
Went over life safety items with contractor 3/10/2005 8:53:57 AM
FIR04-00593 INSP-Sprinkler Rough-in/Hydro3/9/20053/9/20053/9/2005 12:00:00 AMPPASS
kerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles

2" main running east to west, top floor, south bedroom, 2 X 11/2" X 1, shop thread tee leaked, will be repaired. East attic upright, in the top floor north bedroom is obstructed and needs corrected. Other grooved coupling (3 or 4) leaking appeared to stop after field adjustments. JWA
BLD03-02084 FIRE-Final Inspection3/9/20053/9/20053/9/2005 12:00:00 AMPFAIL
Need to final the fire alarm permit. Add exit signs on east end of all floors as discussed and provide two additional fire extinguishers, one near the pool area and one near front desk 3/10/2005 3:49:09 PM
FIR04-00666 INSP-Sprinkler Rough-in/Hydro3/9/20053/9/20053/9/2005 12:00:00 AMPCANC
not ready until tomorrow 3/9/2005 12:56:19 PM