Inspections for the day of: Friday, March 9, 2007.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-02401 FIRE-Final Inspection3/8/20073/9/20073/12/2007 11:12:30 AMPPART
Items on correction notice issued at the previous inspection on 3/7 have been verified for compliance. Agreed to proceed with the terms of the agreements outlined at the on site meeting on 2/16 for temp. storage of the PODS.
FIR06-00396 INSP-Final Inspection3/9/20073/9/20073/12/2007 11:05:08 AMPPASS
Final sprinkler inspection passed, noted missing ceiling tile at one location in front of the womens restroom to be installed today per Sam of Unico.
FIR06-00595 INSP-Alarm Testing3/7/20073/9/20073/12/2007 11:01:47 AMAFAIL
Inspection for the 5th floor Office supply tenant alarm work failed due to non-functional speakers at several locations, two SD have incorrect descriptors, as-built plans should reflect field changes, the notification and initiation devices at the north hall are not installed at this time. Also verified added SS at the mech. penthouse. Attempted test of the 1st floor atrium doors failed due to non-functional manual pull station at the reception desk.
FIR07-00162 INSP-Final Inspection3/8/20073/9/20073/9/2007 11:31:10 AMAPASS
Fire sprinkler permit finaled.
BLD06-03623 FIRE-Final Inspection3/8/20073/9/20073/9/2007 11:30:05 AMAPASS
c/n items are compliant, fire life safety passed.
FIR06-00976 INSP-Final Inspection3/8/20073/9/20073/9/2007 11:28:42 AMAPASS
Final fire sprinkler permit work inspection is satisfactory, permit finaled.
FIR06-00101 INSP-Sprinkler Rough-in/Hydro3/8/20073/9/20073/9/2007 11:26:21 AMAFAIL
Correction notice items from the previous inspection for the antifreeze system completed on 2/27/07 are not complete, also noted to contractor some items still in need of completion including OH floors 1-4 and UG supply hydro tests, missing heads in the gravity chute, and remaining OH inspections.