FIR07-01041
| INSP-Final Inspection | 3/9/2010 | 3/9/2010 | 3/12/2010 7:01:10 AM | P | PART |
|
|
Scope of permit work appears satisfactory, however noted non-compliant spacing at an adjacent training room indicated as "OK" on plans.
|
FIR10-00078
| INSP-Final Inspection | 3/8/2010 | 3/9/2010 | 3/9/2010 4:45:51 PM | P | PASS |
|
|
Scope of fire sprinkler system modifications completed satisfactory, permit finaled. NOTE: concealed space below the stage filled with non-combustible insulation to meet exceptions allowed per NFPA 13.
|
BLD09-02218
| FIRE-Final Inspection | 3/9/2010 | 3/9/2010 | 3/9/2010 4:41:45 PM | P | FAIL |
|
|
Need to provide EM lighting per plan at two locations, post signage at door to the sprinkler antifreeze manifold riser per review note # 16, project attatched fire sprinkler permit final pending missing ceiling tile and escutcheons at some areas. Remainder of fire life safety items okayed.
|
FIR09-00501
| INSP-Final Inspection | 3/8/2010 | 3/9/2010 | 3/9/2010 4:36:17 PM | A | PART |
|
|
Permit work okay for final pending plan modification for upright protection only at this time in room 319, installation of ceiling tile for sprinkler heads at three locations, missing two 401 style canopies and one semi-recessed.
|
FIR10-00011
| INSP-Sprinkler Rough-in | 3/8/2010 | 3/9/2010 | 3/9/2010 4:31:39 PM | A | PART |
|
|
OH is approved for cover at the second and third floors per plan initialed with today's date, discussed rough-in modifications at the first floor in progress.
|
BLD10-00116
| FIRE-Final Inspection | 3/8/2010 | 3/9/2010 | 3/9/2010 4:27:29 PM | A | PASS |
|
|
Fire life safety is satisfactory, inspection passed.
|
FIR10-00095
| INSP-Final Inspection | 3/8/2010 | 3/9/2010 | 3/9/2010 4:22:47 PM | A | PASS |
|
|
Fire alarm testing passed, scope of permit work finaled.
|