BLD09-02220
| FIRE-Final Inspection | 3/8/2010 | 3/9/2010 | 3/9/2010 5:27:02 PM | P | FAIL |
|
|
Provide approved single action hardware on the secondary front exit and the rear exit as discussed. All other items are ok.
|
FIR03-00510
| FIR-Aging Inspection | 3/9/2010 | 3/9/2010 | 3/9/2010 3:19:42 PM | | NR |
|
|
Permit information was forwarded to Scott for further action with non responsive contractor.
|
FIR03-00381
| FIR-Aging Inspection | 3/9/2010 | 3/9/2010 | 3/9/2010 3:18:58 PM | | NR |
|
|
Permit information was forwarded to Scott for further action with non responsive contractor.
|
FIR08-00636
| INSP-Final Inspection | 3/9/2010 | 3/9/2010 | 3/9/2010 3:16:59 PM | P | PASS |
|
|
Permit finaled.
|
FIR08-00772
| INSP-Final Inspection | 3/9/2010 | 3/9/2010 | 3/9/2010 3:04:17 PM | P | PASS |
|
|
Permit finaled.
|
FIR09-00734
| INSP-Sprinkler Rough-in | 3/9/2010 | 3/9/2010 | 3/9/2010 2:20:37 PM | P | PASS |
|
|
The rough-in inspection based on the resubmitted/as-builts passed. We could not gain access to the riser room for an inspection there.
|
FIR09-00681
| INSP-Sprinkler Rough-in | 3/8/2010 | 3/9/2010 | 3/9/2010 2:03:33 PM | P | FAIL |
|
|
Resubmittals are required due to pipe routing and sizing that differs from the approved plans. One pendant on the second floor needs to be relocated since it exceeds 8' from the kitchen wall. There is shadowing in the second floor bathroom. An additional head will be required or a lintel/soffit installed as discussed.
|
FIR09-00731
| INSP-Final Inspection | 3/9/2010 | 3/9/2010 | 3/9/2010 1:22:40 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00731
| INSP-Sprinkler Rough-in | 3/8/2010 | 3/9/2010 | 3/9/2010 11:54:53 AM | A | PASS |
|
|
Permit finaled
|
BLD09-02174
| FIRE-Final Inspection | 3/8/2010 | 3/9/2010 | 3/9/2010 10:07:30 AM | A | PASS |
|
|
life safety passed
|