Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00049 INSP-Final Inspection3/8/20123/9/20123/9/2012 2:56:13 PMPPASS
permit finaled.
BLD12-00187 FIRE-Final Inspection3/9/20123/9/20123/9/2012 2:48:38 PMPPART
A temporary is given with Deputy Chief Romeo's permission until the fire alarm issues have been resolved.
BLD12-00187 FIRE-Conference3/8/20123/9/20123/9/2012 2:10:05 PMPDONE
Met and discussed the fire alarm issues with Mary, Lisa and three other people.
BLD11-02974 FIRE-Conference3/9/20123/9/20123/9/2012 2:09:00 PMPDONE
I met Mike Jordan and the building superintendant and discussed the apparent combustible concealed space at the main entry. New sheating being installed is fire rated but the existing sheating appears not to be fire rated. Therefore sprinkler protection will be required or meeting one of the exceptions in chapter 8 of NFPA 13.
BLD12-00127 FIRE-Final Inspection3/8/20123/9/20123/9/2012 11:31:41 AMAFAIL
Provide annual inspection for the existing fire sprinkler system, provide verification of monitoring and power up the fire alarm system, provide fire extinguishers with current inspection tags place within 75' of travel mounted in a normal path of travel between 5' and 4: A.F.F., provide exit discharge lighting and the missing exit sign per the plans, remove the dead bolt from the rear door, repair the hole in the riser room wall (one hour separation required) and resubmit plans showing the door/wall assembly in the exit corridor and add exit sign/emergency lighting as shown.
FIR12-00123 INSP-Sprinkler Rough-in3/8/20123/9/20123/9/2012 11:25:34 AMAPASS
Sprinkler piping is ok to cover.
BLD12-00071 FIRE-Final Inspection3/8/20123/9/20123/9/2012 10:40:21 AMAPASS
Fire life safety passed