Inspections for the day of: Wednesday, March 9, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00427 Final3/9/20163/9/20163/9/2016 3:19:50 PMPPASS
Please call Joe General Contractor 30 minutes before arrival Phone #: ###-#### Inspection requested via web by Don Conley final ok
ELE16-00016 Final3/9/20163/9/20163/9/2016 3:01:13 PMPPASS
Phone #: ###-#### Inspection requested via web by Kendra Lanham final ok
ELE15-03762 Final3/9/20163/9/20163/9/2016 2:25:23 PMPPASS
Back door is open Phone #: ###-#### Inspection requested via web by Jim Williams final ok
ELE12-01786 ELE-Aging Inspection3/9/20163/9/20163/9/2016 2:02:20 PM DONE
too busy
ELE16-00580 Rough-In Permanent Service3/9/20163/9/20163/9/2016 2:01:25 PMPCANC
UFER inspection for permanent service and fire pump service. Call Lonny for any questions. Thanks Phone #: ###-#### Inspection requested via web by Lonny Baum just needed r/i
ELE16-00580 Electrical Rough-In3/9/20163/9/20163/9/2016 2:00:16 PMPPASS
UFER inspection for permanent service and fire pump service. Call Lonny for any questions. Thanks Phone #: ###-#### Inspection requested via web by Lonny Baum r/i ok concrete encased electrode for MSBs and fire pump controller
ELE15-03461 Final3/8/20163/9/20163/9/2016 1:32:34 PMPPASS
Lock Box Code Is 1993 Outlet Is now GFCI Protected And Ready For Final Thanks Dave Phone #: ###-#### Inspection requested via web by jason shifflett correction made final ok
ELE16-00353 Final3/9/20163/9/20163/9/2016 1:19:11 PMPFAIL
Phone #: ###-#### Inspection requested via web by kendall bender 210.8-all 120volt receptacles in other than dwellings shall have GFCI protection.(across from toilet)
ELE16-00217 Final3/9/20163/9/20163/9/2016 12:56:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Eric Brown final ok
ELE16-00303 Conference3/9/20163/9/20163/9/2016 11:33:10 AMADONE
Need to verify working clearances for HVAC control boxes above ceilings. Phone #: ###-#### Inspection requested via web by Toby Groves 110.26(A)(1)- Working space for equipment operating at 600 volts or less to ground and likely to require examination, adjustment,service or maintenance while energized shall comply with the deminsions 0f 110.26(A)(1),(A)(2) and (A)(3)
ELE16-00303 Electrical Rough-In3/9/20163/9/20163/9/2016 11:21:59 AMPPASS
Need to verify working clearances for HVAC control boxes above ceilings. Phone #: ###-#### Inspection requested via web by Toby Groves r/i ok exterior walls on stairwell 3 between parking structure and city center bldg. level 1 thru 4.
ELE16-00152 Final3/8/20163/9/20163/9/2016 10:03:25 AMAFAIL
Door code 234 Phone #: ###-#### Inspection requested via web by Chris Chesnut 210.8(B)(7)- receptacles within 6 foot of sink shall have GFCI protection (back wall of bar), 110.16-Arc flash warning label on loadcenters, caulk walk in penetrations, old AC cable put in box or cut off.
ELE15-04012 Electrical Rough-In3/8/20163/9/20163/9/2016 9:29:12 AMAPASS
Need partial inspection, we have spoken to Darrell and he is aware of the reason we need partial inspection. Phone #: ###-#### Inspection requested via web by Lori Stout r/i ok electircal room area underslab raceways ok
ELE16-00091 Final3/8/20163/9/20163/9/2016 8:52:53 AMAPASS
Contact is Ben Macdonagh Phone #: ###-#### Inspection requested via web by Scott Campbell final ok
ELE16-00704 Final3/8/20163/9/20163/9/2016 8:16:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Randy Fletcher correct breaker installed final ok